Descargar Imprimir esta página

Waeco ASC 5500G RPA Instrucciones De Uso página 98

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Initial start-up
3. Use the cursor keys  or  to select "Int. vessel filling":
4. Press ENTER to confirm.
5. Then follow the instructions in the display and provided here:
Press ENTER to confirm.
The maximum refrigerant quantity which can be added appears in
the display.
Enter the required amount and press ENTER to confirm.
The internal refrigerant vessel is filled.
When the filling process is finished, this will be confirmed by an
acoustic signal after the analysis.
Close the valves and press ENTER to confirm.
6. After filling, the quantity of refrigerant in the internal container is dis-
played. Press STOP to exit the menu.
Press STOP again to access the standby menu. The unit is now
ready for operation.
98
Int. vessel filling
Flushing
Reset scales.
Service.
Connect the HP hose
to the external tank
then open the valve
ENTER-OK STOP-EXIT
Set the quantity,
then confirm!
ENTER-OK STOP-EXIT
ASC5500G RPA
g.
13620
EN

Publicidad

loading