Descargar Imprimir esta página

Daikin FTX09BXVJU Manual De Instrucciones página 7

Publicidad

Idiomas disponibles

Idiomas disponibles

INDOOR/OUTDOOR UNIT INSTALLATION DRAWINGS
Front panel
1-15/16" (50mm) or more
from walls (on both sides)
Air filters
(M4 x 12L)
Titanium apatite deodorizing filter (2)
Titanium apatite
deodorizing filter
Air filter
Filter frame
Tab
Max. allowable piping length
Min. allowable piping length
Max. allowable piping height
Additional charge required for refrigerant
pipe exceeding 32-13/16 ft (10m) in length
Gas pipe
Liquid pipe
* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
** The suggested shortest pipe length is 10ft (3m), in order to avoid noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used.)
2-3/16" (55mm) or more
from ceiling
Screws
Service lid
The service lid is removable
 Opening method
1) Remove the service
lid screws
2) Pull out the service lid
diagonally down in the
direction of the arrow.
3) Pull down.
Allow 11-13/16" (300mm) of work
space below the ceiling surface.
Where there is a danger of
the unit falling, use foot bolts.
RX(B)/RK09
65-5/8 ft (20m)
49-1/4 ft (15m)
3/8 inch (9.52mm)
Caulk pipe
hole gap
with putty.
Cut thermal insulation pipe
to an appropriate length and
wrap it with tape, making
sure that no gap is left in the
insulation pipe's cut line.
Wrap the insulation pipe
with the finishing tape from
bottom to top.
Refrigerant piping must be
protected from physical damage.
Install a plastic cover or equivalent.
Allow space for piping
and electrical servicing.
RX(B)/RK12
RX(B)/RK18
10 ft (3m)
0.21 oz/ft (20g/m)
1/2 inch (12.7mm)
1/4 inch (6.35mm)
1-5
Stop valve cover
 How to remove the stop valve cover.
• Remove the screw on the stop
valve cover.
• Slide the lid downward to
remove it.
 How to attach the stop valve cover.
• Insert the upper part of the stop
valve cover into the outdoor
unit to install.
• Tighten the screws.
RX(B)/RK24
98-1/2 ft (30m)
65-5/8 ft (20m)
5/8 inch
(15.88mm)

Publicidad

loading