Make DTT cooling unit - Performance-Cut cut-outs
1
4
3
Pos
Designation
1
Unit contour
3
Cutline / cabinet depth 400 mm (15.75 in)
The "Performance-Cut" switch cabinet cut-out (4) guarantees full performance of the cooling unit with minimal
power consumption. It is also well-suited for cooling units with a flat channel system; see
Make cut-outs for the DTT cooling unit
Requirements
- All general requirements are fulfilled, see
-
The cooling unit is de-energized.
Required tools and material
-
Saw
-
Use a switch cabinet cutter, if applicable
-
Protective covers
Procedure
Use a protective cover to protect the switch cabinet from chips.
Provide the switch cabinet with cut-outs and holes. For the prescribed dimensions, refer to the figure
"Easy-Cut"
or
"- Performance-Cut
Deburr the cut edges.
Remove chips and assembly waste from the switch cabinet.
Cut-outs (4) and holes have been made.
Operating Manual DTT 6101 / 6201 Multicontroller (MC) 086100023a © Pfannenberg GmbH
Performance-Cut" switch cabinet cut-out
Figure18 - DTT "
General assembly requirements
cut-outs".
Pos
Designation
2
Cut-out angle 60°
4
General view: DTT cooling unit and cut-out
2
flat
channel system
.