GB
4.2
Multicontroller operation
1
2
6
Figure 34- Control panel (MC)
The control panel has four menu settings that are displayed on the LCD (1).
LCD display
Menu setting
SetP: Switch cabinet temperature setpoint
Lit¯: Maximum switch cabinet temperature value (high limit value)
Lit_: Minimum switch cabinet temperature value (low limit value)
Unit: Unit of the switch cabinet temperature
4.3
Carrying out menu settings
Requirement
-
Cooling unit has started operation.
-
LED light (6) of the control panel illuminates green.
Procedure
Scroll through the menus (SetP, Lit¯, Lit_, Unit) from the temperature display (1) with the SCROLL UP (3) and
SCROLL DOWN (4) buttons.
Select a menu with the SET button (5).
Enter the password. After pressing the SET button (5) press the SCROLL UP (3) and SCROLL DOWN (4)
buttons within two seconds; see Password button combination figure.
Always adjust the desired value with the SCROLL UP (3) and SCROLL DOWN (4) buttons.
Confirm the value with the SET button (5).
When the BACK button (2) is pressed, the value is not saved.
Select a different menu by scrolling with the SCROLL UP (3) and SCROLL DOWN (4) buttons.
If there is no input for 30 seconds, a TIMEOUT is initiated and the LCD switches to temperature display.
Menu is adjusted in the cooling unit.
Operating Manual DTT 6101 / 6201 Multicontroller (MC) 086100023a © Pfannenberg GmbH
4
5
3
1
Password
5
3
1
< 2s
Figure 35 - Password button combination (MC)
4
< 2s
Input
0 – 90 °C
- 55 – 95 °C
- 55 – 95 °C
°C / °F
Page 34 / 50