Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The LED DL12 flashes green 6 times when the memory is full (1000 codes). Now LED DL12
blinks red for 10 s enabling possible cancellation of all codes.
3 - Re-set DIP 1 to OFF and DIP 2 to OFF.
G - RADIO CODES PROGRAMMING PROCEDURE FOR PEDESTRIAN OPENING (1000
CODES MAX) - with radio module ACG8069
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. DL12 flashes green for 10 s.
2 - Press the transmitter button (usually channel B) within the allotted 10 s. If the transmitter
is properly memorized LED DL12 blinks red and the buzzer emits a tone. The 10 s are
automatically renewed (DL12 flashes green) in order to memorize next transmitter.
3 - To finish programming wait 10 s, or press the PROG button briefly. The LED DL12 stops
flashing.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
ALL RADIO CODES FOR PEDESTRIAN OPENING CANCELLATION PROCEDURE
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. LED DL12 flashes green for 10 s.
2 - Press and hold the PROG button for 5 s. Memory cancellation is indicated by two red flashes
of LED DL12 and two tones of the buzzer.
3 - The red LED DL1 remains active and you can add new codes as shown above.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
RADIO CODES MEMORY FULL INDICATOR (FOR PEDESTRIAN OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - LED DL12 flashes green 6 times if the memory is full (1000 codes). LED DL12 blinks red for 10
s enabling possible cancellation of codes.
3 - Set DIP 1 to OFF and DIP 3 to OFF.
H - PROGRAMMING RADIO CODES (FOR R-AUX RELAY) (1000 CODES MAX) - with
radio module ACG8069
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. DL12 flashes orange for 10 s.
2 - Press the transmitter button (usually channel C) within the allotted 10 s. If the transmitter
is properly memorized LED DL12 blinks green and the buzzer emits a tone. The 10 s are
automatically renewed (DL12 flashes orange) in order to memorize next transmitter.
3 - To finish programming wait 10 s, or press the PROG button briefly. The LED DL12 stops
flashing.
4 - Reset DIP 1, 2, 3 to OFF.
RADIO CODES CANCELLATION PROCEDURE (FOR R-AUX RELAY)
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. LED DL12 flashes green for 10 s.
2 - During these 10 s press and hold the PROG button for 5 s. Memory cancellation is indicated
by two green flashes of LED DL12 and two tones of the buzzer.
3 - LED DL12 blinks orange again for 10 s and you can add new codes as shown above.
4 - Re-Set DIP 1, 2, 3 to OFF.
RADIO CODES MEMORY FULL INDICATOR (FOR R-AUX RELAY)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON.
2 - LED DL12 flashes green 6 times if the memory is full (1000 codes). LED DL12 blinks red for 10
s enabling possible cancellation of codes.
3 - Re-Set DIP 1, 2, 3 to OFF.
FUNCTIONING OF CONTROL ACCESSORIES
STEP-BY-STEP BUTTON (COM A+/START)
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the gate
re-opens.
OPEN BUTTON (COM A+/OPEN)
The button controls the opening movement when the gate is stationary. If activated while
closing, it re-opens the gate.
B.I.O. BUTTON - OPENS WITH CLOCK FEATURE (COM A+/B.I.O.)
This function is useful during peak hours, when vehicle traffic is slow (e.g. entry/exit of
workers, emergencies in parking or residential areas and, temporarily, for moving operations).
By connecting a switch and/or a daily/weekly clock to COM A+/B.I.O., you can open and keep
the automation open for as long as the switch is pressed or the clock remains active. When the
gate is open, all the commands are ignored.
Releasing the switch or at the end of the set time, the automation closes immediately.
CLOSE BUTTON (COM A+/CLOSE)
Controls the closing movement when the gate is stationary.
TRANSMITTER
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the gate
reopens.
PEDESTRIAN OPEN BUTTON (COM A+/PED.)
Partial opening and closing control.
During pedestrian opening, pausing or closing, you can control the opening of any command
linked to the L1 board.
With DIP 6 you can choose the operation mode of the pedestrian push button.
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the gate
reopens.
FUNCTIONING OF SAFETY ACCESSORIES
PHOTOCELLS (COM A+/PHOT 1, COM A+/PHOT 2)
NOTE: the transit through the photocells is signaled by a buzzer tone
DIP 4 OFF => if an obstacle is placed in range of the photocells when the gate is closed, the gate
does not open. During operation, photocells work when opening (by starting the
opening movement only after the obstacle is removed) and closing (by starting
the reverse movement only after the obstacle is removed).
DIP 4 ON => if an obstacle is placed in range of the photocells when the gate is closed and
the command to open is given, the gate opens (the photocells do not work while
opening). Photocells work only during closing (with reverse motion restored after
a second, even if they are still engaged).
ATTENTION: In case the receiver led remains lit, malfunctioning of the main supply is
suspected.
It is advisable to connect electrically to earth the columns
or the photocells stands to the terminal A -, to shield the
photocells from external noise.
Be careful not to short circuit the system when the supply
phases are inverted!
MONITORING OF PHOTOCELLS (A+ TEST A-)
Connect the photocell transmitter to A+ TEST/A- and set DIP 7 to ON.
The monitoring consists of a functional test of the photocell run before every movement.
The gate movement is therefore permitted only if the photocells have passed the functional
test.
CAUTION: MONITORING OF THE PHOTOCELLS INPUTS (PHOTO 1/PHOTO 2) CAN BE ACTIVATED WITH
DIP 7 ON OR DEACTIVATED WITH DIP 7 OFF.
WARNING: If the AUTOTEST feature is enabled and only one photocell is connected, a jumper
must be made between the PHOT 1 and PHOT 2 terminals. If the jumper is not made,
the AUTOTEST fails and the gate will not move.
PHOTOCELL AUTOTEST ALARM (DIP 7 ON)
If the photocell fails the monitoring test, an alarm is displayed by the blinker lighting up
and gate movement is not allowed. Normal operation can be restored only by repairing the
photocell and pressing one of the controls.
EDGES (SAFETY STRIPS) (COM A+/EDGE 1, COM A+/EDGE 2)
If engaged when closing, EDGE 1 reverses the motion in opening. If edge remains engaged, it
doesn't permit the closing.
If engaged during opening, EDGE 2 reverses the motion in closing. If edge remains engaged, it
doesn't permit the opening.
If edges are not used, jump the terminals COM A+/EDGE1/EDGE2.
EDGE ALARM
Flasher and buzzer are activated with 2 tones every 5 s for one minute.
STOP BUTTON (COM A+/STOP)
The STOP button stops the gate during any operation.
35