Risk of air blast!
!
Continuously check CO, CO 2 and soot emissions when adjusting the output of the burner. Optimise combustion values in the
event of CO formation. CO must not exceed 50 ppm.
Gas pressure diagrams in appendix
Minimum gas pressure required are
indicated in the diagrams in the appendix.
These values have been determined in
our test labs and are useful for the first
switch-on as final setting must be done
using a combustion analyzer.
How to read and adjust the values:
- determine the output required
- determine the combustion chamber back-
pressure
- read the minimum gas pressure required
in the diagrams in appendix.
Optimising combustion values
The factory setting shall be modified
MAX GAS 170 PAB NATURAL GAS
6,0
5,5
5,0
4,5
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
-0,5
-1,0
-1,5
40
50
60
70
80
420010029201
Firing head setting (B).
To act on the screw in fi gure:
• turn Allen key till you reach the
requested value (index 0-4,5).
according to the output requeired.
The diagrams of air/head setting
that are available in the appendix
of this manual are a guide for ensuring
that the burner functions as well as
possible.
9,5
9
0
1
2
90°
90°
90°
90
100
110
120
130
140
150
output (kW)
8,5
8
3
90°
160
170
180
190
200
210
220
Adjustment of gas solenoid valve
Refer to the gas train manual for the gas
setting of the gas train selected.
N.B. observe the minimum required
flue gas temperature specified by the
boiler manufacturer and the requirements
demanded of ue gas ducts for avoiding
condensation.