Symbols; Safety Information; Warnings And Precautions - Amprobe RS-3 PRO Manual De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 44

SymbOLS

SAfETy INfORmATION

The RS-1007 Pro and RS-3 Pro Analog Clamp meters conform to
EN61010-1:2001; EN61010- 2-032:2002; CAT IV 600 V, class II and pollution
deg.2
This instrument is EN61010-1 certified for Installation Category IV (600V).
It is recommended for use in primary supply lines, overhead lines and
cable systems and distribution level and fixed installations, as well as lesser
installations.
Do not exceed the maximum overload limits per function (see
specifications) nor the limits marked on the instrument itself. Never apply
more than 600 V ac rms between the test lead and earth ground.
 Warnings and Precautions
Before and after hazardous voltage measurements, test the voltage
function on a known source such as line voltage to determine proper
meter functioning.
Disconnect the test leads from the test points before changing meter
functions.
Disconnected from the meter's test leads before measuring current.
Inspect the Clampmeter, test leads and accessories before every use. Do
not use any damaged part.
Never ground yourself when taking measurements. Do not touch exposed
circuit elements or test probe tips.
Do not operate the instrument in an explosive atmosphere.
To reduce the risk of fire or electric shock, do not expose this product to
rain or moisture.
The meter is intended only for indoor use. To avoid electrical shock
hazard, observe the proper safety precautions when working with
voltages above 60 VDC, 42.4 Vpk, or 30 VAC rms. These voltage levels pose
a potential shock hazard to the user.
Before and after hazardous voltage measurements, test the voltage
function on a known source such as line voltage to determine proper
meter functioning.
Keep your hands/fingers behind the hand/finger barriers (of the meter
and the test leads) that indicate the limits of safe access of the hand-held
part during measurement.
Inspect test leads, connectors, and probes for damaged insulation or
exposed metal before using the instrument. If any defects are found,
replace them immediately.
This Clamp-on meter is designed to apply around or remove from un-
insulated hazardous live conductors. Individual protective equipment must
be used if hazardous live parts of the installation could be accessible.
Exercise extreme caution when: measuring voltage >20 V // current >10
mA // AC power line with inductive loads // AC power line during electrical
storms // current, when the fuse blows in a circuit with open circuit voltage
>1000 V // servicing CRT equipment.
Remove test leads before opening the case to change the battery.
 CAUTION
For non-invasive ACA current measurements, clamp the jaws around only
one single conductor of a circuit for load current measurement. More than
1 conductor will cause false readings.
 CAUTION
Verify the needle lock is released before making measurements.
Battery
Double insulated
Alternating Current
Conforms to relevant
Australian standards.
Do not dispose of this
product as unsorted
municipal waste.
Application around and removal from hazardous live
conductors is permitted
Refer to the manual
Dangerous Voltage
Earth Ground
Complies with EU
directives
Underwriters
Laboratories.[Note:
Canadian and US.]
5

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Rs-1007 pro

Tabla de contenido