Beninca ZED24 Manual De Instrucciones página 9

Ocultar thumbs Ver también para ZED24:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
Terminal No.
Function
1-2
+ M2
3-4
- M2
7-8
Motor 2 light
9-10
COM
11-12
SWC
13-14
SWO
a) If present, the push buttons on the motor are connected to Step-by-Step and STOP controls.
Any further safety devices should be connected in series to the STOP control.
b) The courtesy light stays on for about 90s at each operation.
c) The safety EDGE should be connected only to the special inputs. Two types of EDGE can be used:
If a safety edge is used with 8K2 resistance, the "DAS" jumper should be closed.
If a mechanical safety edge with N.C. contact is used, the "DAS" Jumper should be opened.
If no edge is used, terminals 23-24 should be short-circuited, the "DAS" Jumper should be opened.
1) Power the control unit
2) Manually release the system and completely open the door.
3) Adjust the opening limit switch cam, the SWO LED turns off.
4) Shut the door completely.
5) Adjust the closing limit switch cam, the SWC LED turns off.
6) Cut off power supply.
7) Move the door half-way and lock it again.
8) Reset power supply. The STOP, PHOT, SWO and SWC LED's should light up.
9) Give a step-by-step control signal by pressing the appropriate button or using the remote control.
10) The door should move in the opening phase. In the negative, it is sufficient to invert the speed wires (15<>16) of the motor and
the limit switch inputs (SWO<>SWC).
11) Adjust Time, the Operating Logistics as well as the Motor speed.
To enable the slowdown feature during opening and closing set Dip-Switch 3 to ON.
Preset the braking speed by using Dip-Switch 7.
The braking phase will start when the limit switches are triggered and will last for 4", of which 3" at reduced torque and 1" at
maximum torque.
During the slowdown cycle the amperometric sensor is disabled. Make sure that, during the closing slowdown cycle the gate does
not travel more than 5 cm of the stroke.
WARNING! This adjustment affects the safety level of the automatic system.
Make sure that the force applied onto the gate wing complies with regulations in force.
The supply transformer is provided with a Faston (VMOT) connector which permits to adjust the motor speed at three different levels.
When the Faston (VMOT) is on 15, the speed is at minimum. When the Faston is moved to 23, the maximum speed is obtained.
AMP-O This trimmer allows to adjust the activation threshold of the current sensor in the opening phase.
When the sensor is triggered in the opening phase, the motor stops.
AMP-C This trimmer allows to adjust the activation threshold of the current sensor in the closing phase.
The sensor activation in the closing phase causes the total re-opening of the door. A new closing operation is then
immediately started.
In the event of a new amperometric activation, the operation is carried out again. If none of the three closure operations is
completed, the door will stay completely open.
N.B.: At the beginning of the closing operation, the motor operates at maximum torque for approx. 1.5". In this phase the
amperometric sensor is disabled and remains disabled until the SWO opening limit switch is relased.
TCA
It allows to adjust the automatic closure time. Check Dip-Switch N°1= On.
The adjustment varies from 1s minimum to 90s maximum
ZED24 SC Card
Description
+ connection of motor 2
- connection of motor 2
Connection to courtesy light of Motor 2
Common, limit switches of Motor 2.
Input, CLOSE limit switch
Input, OPEN limit switch
REMARKS:
TO ADJUST THE LIMIT SWITCHES
ENABLING THE SLOWDOWN FEATURE
TO ADJUST SPEED
FUNCTION OF TRIMMERS
9

Publicidad

Tabla de contenido
loading

Tabla de contenido