Installation
4.4
Electrical connections
Rated
Voltage
Model
(V)
US12
240
Table 5
B Strip back the insulation on the power wires about 3/
8". Any insulation on the ground should be stripped
back about 3/4".
B Feed the cable through the cover bottom or backplate
entry grommets, as appropriate.
B Connect the cables to the terminal block and ground
stud (Fig. 3):
Rubber
Sleeve
Fig. 3
Cable termination
NOTE:
When the AE 12 is not within sight of the
electrical circuit breakers, a circuit breaker
lockout or additional local means of
disconnection for all non grounded
conductors must be provided that is within
sight of the appliance. (REF NEC 422.31)
B Make sure that all the terminal block screws are
tightened securely. Loose connections can cause
wires to neat up.
B Make sure that the ground wire is wrapped around its
terminal stud and into the saddle washer. The nut
should be tightened securely.
10
Rated
Recommend
Current
Wire Size
(A)
(AWG)
50
6
Ground
B Attach the front cover and tighten the retaining
screws.
6 720 800 531 (2011/09)