Disposal; Spare Parts; Alarms - Calpeda e-idos E-MXPM Instrucciones De Uso

Sistema de presurización con control integrado
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 34

10. DISPOSAL

OFF
The final disposal of the device must be done by
EN
specialized company.
Make sure the specialized company follows the
classification of the material parts for the separation.
Observe the local regulations and dispose the device
accordingly with the international rules for environment
protection.

11. SPARE PARTS

11.1.
Spare-parts request
When ordering spare parts, please quote their
designation, position number in the cross section
drawing and rated data from the pump name plate
(type, date and serial number).
The spare parts request shall be sent to CALPEDA
S.p.A. by phone, fax, e-mail.
11.2.
ESIGNATION OF PARTS
Nr.
Designation
14.00 Pump casing
14.04 Plug
14.06 O-ring
14.12 Plug
14.16 O-ring
14.20 O-ring
14.24 Screw
14.47 O-ring
14.64 Valve, set
14.66 Washer / Retaining ring
16.00 Suction casing
16.14 Plunger
16.15 Spring
16.16 O-ring
16.17 Valve
20.00 Delivery casing
22.00 Ejector
22.12 O-ring
22.16 O-ring
25.01 First stage casing

12. ALARMS

Error reset can be automatic or manual, depending on the error that occurs. Manual reset is carried out using the
enter button and then start to restart the pump.
Code
Description
Er01
Blockage due to no water
Er02
Faulty pressure sensor – Max. ressure exceeded
Er03
Blockage due to low supply voltage
Er04
Blockage due to high rectified voltage
Er05
Blockage due to exceeded of number of starts
Er06
Blockage due to overpower in the electro pump
Er07
Blockage due to overcurrent in the electro pump motor
Er08
Blockage due to internal overheating
Er09
Blockage due to overpressure
Er10
Thermal-protector intervention detected
Er11
Internal hardware error
Page 16 / 72
European Directive
2012/19/EU (WEEE)
25.02 Stage casing (complete)
25.05 Last stage casing
25.10 Washer for missing impeller
25.11 First stage spacer
26.00 Diffuser
26.06 O-ring
28.00 Impeller
28.04 Impeller nut
28.08 Washer
28.12 Circlip
34.00 Casing cover
36.00 Mechanical seal
36.51 Retaining ring, split
36.52 Shoulder ring
46.00 Deflector
64.15 Spacer sleeve
70.00 Lantern bracket
73.00 Ball bearing
76.00 Motor casing with winding
76.04 Cable gland
76.16 Support
76.54 Terminal box, set
78.00 Shaft with rotor packet
81.00 Ball bearing
82.00 Motor end shield
82.04 Compensating spring
88.00 Motor fan
90.00 Fan cover
90.04 Screw
92.00 Tie-bolt
94.00 Capacitor
94.02 Capacitor gland
98.00 Terminal box cover
98.04 Screw
98.08 Gasket
98.20 Screw
98.51 Transducer
98.52 Signals cable
98.53 Main power cable
98.55 Terminal box cover with board
Reset ERR
Causes
The device is in failure due to no water.
MAN
The system try to restart automatically and make one
attempt every 10 minutes for 7 times.
MAN
Faulty pressure sensor
Supply voltage lower than 195V.
AUT
- The system automatically restart when the clamp
voltage is higher than 205V.
Supply voltage higher than 225V.
AUT
- The system automatically restart when the clamp
voltage is lower than 225V.
MAN
The system has started more than 240 times in 2 hours
MAN
The system try to restart automatically and make one
MAN
attempt every 10 seconds for 3 times.
AUT
MAN
MAN
Motor overheating
AUT
E-MXAM E-MXPM E-NGXM Rev4 - Operating Instructions

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

E-idos e-mxamE-idos e-ngxm

Tabla de contenido