Max. Input Current:
"INPUT" jack: 200 mA
"A" jack: 10 A
For measurements > 5 A: duration < 10 seconds, interval > 15 minutes
Voltage Drop:
200 mA /10 A ranges: 200 mV
2 A ranges: 20 mV
AC CURRENT
Range
200 mA
2 A
10 A
Overload Protection:
200 mA ranges: F 0.5 A / 600 V fuse
2 & 10 A ranges: F 10 A / 600 V fuse
Max. Input Current:
"INPUT" jack: 200 mA
"A" jack: 10 A
For measurements > 5 A: duration < 10 seconds, interval > 15 minutes
Voltage Drop: 200 mA / 10 A ranges: 200 mV
2 A ranges: 20 mV
Frequency Range: 40 Hz ~ 400 Hz
Response: True RMS
BATTERY TEST
Range
9 V
1.5 V
Resolution
100 µA
1 mA
10 mA
Resolution
10 mV
1 mV
Accuracy
(1.5 % of rdg + 10D)
(2.0 % of rdg + 10D)
Internal Resistance
910
150