Descargar Imprimir esta página

Salicru EQUINOX SLC EM Lite Manual De Usuario página 76

Publicidad

Idiomas disponibles

Idiomas disponibles

7. SWITCH-ON SEQUENCE.
7.1. CONFIGURATION OF THE SLC EM LITE,
SLC EM AND SLC EM T WITH THE
EQUINOX2 SOLAR INVERTER.
Only power the inverter with DC voltage and switch off the
1.
solar inverter's AC power switch.
Once the inverter display has been switched on, follow the
2.
steps below to change the unit's modbus address (only for in-
stallations with the
From the main menu, press ENT X times, depending on the
a.
number of MPPTs in the unit, until you reach the "General
Settings" menu.
Press for 3 seconds to enter the next "Syst. Info" menu.
b.
Press ENT 13 times until you reach the "Modbus Add."
c.
menu, press for 3 seconds to enter and access the numeric
characters; press ENT repeatedly to increase each digit
until the required one is reached. To change the digit, press
ENT for 3 seconds.
76
ON
OFF
SLC ENERGY MANAGER
device:
x8 (1s)
x9 (1s)
x11 (1s)
x17 (1s)
1 MPPT
2 MPPTs
4 MPPTs
10 MPPTs
x1 (4s)
x1 (4s)
To browse the different menus, a short press (1 second)
allows you to scroll between the screens of a specific
menu, while a  long press (3 seconds) allows access to the
parameters or subscreens of the selected menu.
x1 (4s)
x1 (1s)
x6 (1s)
Wait
x13 (4s)
x1 (4s)
Wait
x6 (1s)
SALICRU

Publicidad

loading

Este manual también es adecuado para:

Equinox slc emEquinox slc em t