INSTALLATION
2.1
BOILER ROOM
The. boilers. with. a. rating. of. more.
than. 35. kW. must. be. equipped. with.
a.technical.room.whose.dimensions.
and.requirements.correspond.to.the.
current.standards.and.regulations..
The.minimum.distance.between.the.
walls. of. the. room. and. the. boiler.
must.not.be.less.than.0.60.m.,.while.
the. minimum. height. between. the.
AQUA HE 25 ErP.BE
AQUA HE 35 ErP BE
top. of. the. boiler. and. the. ceiling.
must. be. at.least. 1. m..which.can. be.
reduced. to. 0.50. m.. for. boilers. with.
incorporated. heaters. (however. the.
minimum. height. of. the. boiler. room.
must.not.be.less.than.2,5.m)..
The.boilers.with.a.rating.of.less.than.
35. kW. can. be. installed. only. in. per-
fectly.air-vented.rooms..
To.circulate.air.in.the.room,.air.vents.
must. be. made. on. the. outside. walls.
2
bar
1
3
0
4
OPEN
which. satisfy. the. following. require-
ments:
–..Have. a. total. surface. area. of. at.
least.6.cm
of. thermal. capacity. and. however.
not.less.than.100.cm
–..To.be.situated.as.close.as.possible.
to. the. floor,. unobstructable. and.
protected. by. a. grate. which. does.
AQUA HE 25 INOX ErP.BE
AQUA HE 35 INOX ErP BE
2
.for.each.installed.Kw.
2
.
2
bar
1
3
0
4
Fig..4
75

Publicidad

loading