Programming Overview
3-9
Menu-
Entry
Selection
No.
point
3
Setting the door's top end-of-travel position
30
Change of direction (press for 5 sec.)
31
Setting the door's bottom end-of-travel position
32
Setting the door's half-open position
50*
Fine adjustment of top end-of-travel position
33
50 - 0
0... 80mm deeper
50 - 99
0... 80mm higher
Fine adjustment of bottom end-of-travel position
50*
34
50 - 0
0... 80mm deeper
50 - 99
0... 80mm higher
Selecting the closing edge
0*
Optical closing edge OSE
35
Electrical safety edge 8K2
1
2
Pressure wave edge DW with testing
Selecting the photocell
0*
without photocell
36
1
2-wire photocell LS2
2
4-wire photocell LS5, Reflection photocell RLK 29
3
Frame fitted photocell LS2
25*
Adjustment pre-limit switch safety edge
37
25 - 0
0... 50mm deeper
25 - 99
0... 100mm higher
- -
4
Selecting the operating modes
0
Dead man OPEN / Dead man CLOSE
40
1*
Impulse OPEN / Dead man COSE
2
Impulse OPEN / Impulse CLOSE
3
AR - automatic closing
4
AR - shortened response time
5
OPEN-CLOSE operation/Red-green-traffic light A800
Response of safety edge
41
0*
Full reversing
1
Partial reversing
Correcting the slowing-down path
42
0
off
1*
on
Level adjustment
0*
off
43
activated for 200 cycles
1
activated for 1,000 cycles
2
Hold-open phase in seconds
0*
0
1
10
2
20
3
30
4
40
5
50
44
6
60
7
90
8
120
9
150
10
180
11
210
12
240
Menu
30-
37
* Factory defaults
Item
1x
Menu-
Entry
No.
Selection
point
4
Status relay X5
0
Door closed signal
1*
Door open signal
45
2
2 minutes garage light
3
5 minutes garage light
4
H
and transmitter
5
Wipe impulse ELTACO
Status relay X6
0*
Door closed signal
1
Door open signal
46
Rotampel ohne Vorwarnzeit
2
3
Red traffic light without early warning phase
4
Red traffic light with 10 seconds early warning phase
Spring breakage detection
47
0*
off
1 - 99
Limit force
Opening force limit
48
0*
off
1 - 99
Limit force
Exit menu
5
Key switch function (J7)
0*
No function
1
Block control panel
2
Block external control elements
50
3
Block control panel and external control elements
4
Activating the control elements for 10 secs.
5
Operating mode impulse OPEN / dead man CLOSE
6
Block button 1/2
Function of external impulse generators
51
0*
Three-button-control
Open-Stop-Close function (J1.3 1/2-opening J1.4 full-opening)
1
52
-
Entering the control address
- -
Exit menu
6
Programming the START button on the hand
60
Programming button for 1/2-opening on the transmitter
61
Programming the light button on the hand transmitter
62
Deleting radio codes (press for 5 sec.)
63
- -
Exit menu
Selecting the door's service intervals
9
0*
no service interval
1
1000 cycles
2
4000 cycles
3
8000 cycles
4
12000 cycles
90
5
16000 cycles
6
20000 cycles
7
25000 cycles
8
30000 cycles
9
35000 cycles
10
40000 cycles
11
45000 cycles
12
50000 cycles
91
Issue of cycles counter
Issue of operating hours counter
96
97
Issue of error memory
-
Issue of
98
99
Resetting of factory setting (press for 5 sec.)
Exit menu
Enter
on / off
-
-
cycles
-
-
hours
-
-
hours
error code
-
-
software version
serial-no.
date
GB
Exit
-
-