Descargar Imprimir esta página

Ecoflam BLU 5000.1 PR Manual De Instrucciones página 17

Quemador de gas progresivos en modulante

Publicidad

Idiomas disponibles

Idiomas disponibles

SELECTOR
COMMUTATORE
AUTO
0
operating elements locked in an intermediate
0 = bloccaggio degli apparati per il
position
funzionamento in una posizione intermadia
operation on maximum capacity
= funzionamento alla massima potenza
operation on minimum capacity
= funzionamento alla minima potenza
automatic operation
AUTO = funzionamento automatico
ADJUSTING THE MINIMUM CAPACITY OF THE BURNER – AIR and GAS
Position the selector placed on the control panel on position 2 and proceed as follows:
Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gas flow,
as established by analyzing the combustion process.
Position the selector, situated on the control panel, on position 1 and proceed as follows:
Adjusting the maximum gas flow rate (see figure on solenoid valve adjustments) or adjust the gas pressure in the gover-
nor.
Adjusting the maximum air flow rate (see figure, detail 2). Loosen the nut holding the air damper transmission rod;
The correct air flow as established by analyzing the combustion process.
Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the position of
the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
CALCULATING THE BURNER CAPACITY
To calculate the burner's capacity in kW, proceed as follows: Check the gas flow rate (in liters) on
the counter and the time of the reading in seconds.
Proceed with the calculation using the following :
AIR ADJUSTMENT
Part. 1
-
-
ADJUSTING THE MAXIMUM CAPACITY OF THE GAS
ADJUSTING THE MAXIMUM AIR FLOW RATE
ADJUSTING THE INTERMEDIATE BURNER CAPACITY
+
Part. 2
e x f = kW
sec
pag.17
LB 832 BLU 5000.1 - 6000.1 PR / MD B
e
sec = Time in second
G20 = 34,02
f
G30 = 116
G31 = 88
- -
+
Part. 3
= Litres gas

Publicidad

loading

Este manual también es adecuado para:

Blu 6000.1 prBlu 5000.1 mdBlu 6000.1 md