Sime SOLO HE 35 ErP BE Instrucciones Para El Instalador página 77

Ocultar thumbs Ver también para SOLO HE 35 ErP BE:

Publicidad

Idiomas disponibles

Idiomas disponibles

from.the.electrodes.
–. Unscrew. the. fixture. screws. of. the.
circulator.support.and.remove.it.
–. Brush.the.propeller.delicately.(tur-
bulence.disc).
–. Carefully. clean. the. photo-resist-
ance. of. eventual. deposits. of. dirt.
deposited.on.its.surface.
–. Clean. the. remaining. components.
of.the.combustion.head.of.eventual.
deposits.
–. Upon. completion. re-assemble. the.
unit.in.the.opposite.way.as.described.
above. taking. care. to. respect. the.
indicated.measurements.
4.7.3
Substitution of nozzle
(fig. 18)
The. nozzle. should. be. substituted. at.
the.beginning.of.every.heating.system.
for.guaranteeing.the.correct.fuel.flow.
and.a.good.spray.efficiency..
The.nozzle.is.substituted.in.the.follow-
ing.manner:
–. Disconnect. the. high. tension. cables.
from.the.electrodes.
–. Loosen. the. fixture. screw. (A. fig..
17). of. the. electrodes. support. and.
remove.it.
–. Block. the. spray. door. using. a. n°19.
spanner. and. unscrew. the. nozzle.
with.a.n°16.spanner.(fig..18).
4.8
FAULT FINDING.
There. follow. a. list. of. some. reasons.
and.the.possible.remedies.for.a.series.
of. faults. which. could. happen. causing.
a. failure. or. an. irregular. function. of.
the.appliance..A.function.fault,.in.most.
cases,.causes.the."lock.out".signal.on.
the.control.panel.to.turn.on..
When. this. light. turns. on,. the. burner.
can.only.function.again.after.the.reset.
button. has. been. pressed;. once. this.
has. been. done. and. a. regular. ignition.
occurs,. the. failure. can. be. defined.
momentary.and.not.dangerous..
On.the.contrary,.if.the."lock.out".per-
sists,. then. the. cause. of. the. fault. as.
well.as.the.remedy.must.be.looked.for.
in.the.following.faults:
The burner does not ignite
–. Check.the.electric.connections.
–. Check. the. regular. fuel. flow,. the.
cleanness.of.the.filters,.of.the.noz-
zle.and.air.vent.from.the.tube.
–. Check. the. regular. spark. ignition.
and.the.proper.function.of.the.burn-
er.
The burner ignites regularly but the
flame goes out immediately
Fig..18
–. Check. the. flame. detection,. the. air.
calibration. and. the. function. of. the.
appliance..
Difficulty in regulating the burner
and/or lack of yield
–. Check:.the.regular.flow.of.fuel,.the.
cleanness. of. the. boiler,. the. non.
obstruction. of. the. smoke. duct,. the.
real. input. supplied. by. the. burner.
and.its.cleanness.(dust)..
The boiler gets dirty easily
–. Check.the.burner.regulator.(smoke.
analysis),.the.fuel.quantity,.the.flue.
obstruction.and.the.cleanness.of.the.
air.duct.of.the.burner.(dust).
CORRECT.POSITION.ELECTRODES
CORRETTA POSIZIONE ELETTRODI
A
The boiler does not heat up
–. Control. the. cleanness. of. the. shell,.
the. matching,. the. adjustment,. the.
burner. performances,. the. pre-
adjusted. temperature,. the. correct.
function.and.position.of.the.regula-
tion.stat.
–. Make. sure. that. the. boiler. is. suf-
ficiently.powerful.for.the.appliance.
Smell of unburnt products
–. Control. the. cleanness. of. the. boiler.
shell. and. the. flue,. the. airtightness.
of. the. boiler. and. of. the. flue. ducts.
(door,.combustion.chamber,.smoke.
ducts,.flue,.washers).
–. Control.the.quality.of.the.fuel.
Frequent intervention of the boiler
shutoff valve
–. Control. the. presence. of. air. in. the.
system,.the.function.of.the.circula-
tion.pumps.
–. Check. the. load. pressure. of. the.
appliance,. the. efficiency. of. the.
expansion.tanks.and.the.valve.cali-
bration.
Fig..17
77