9. TROUBLESHOOTING (
P
ROBLEMS
7. The wall control does
not work OR its indicator
flashes.
8. The push-button timer
does not work OR its
indicator light does not
stay on.
9. The motor does not work.
10. The defrost cycle does
not work (the fresh air
duct is frozen OR the
fresh air distributed is
very cold).
11. The integrated control
push button does not
work.
'
)
CONT
D
P
OSSIBLE CAUSES
• The wires may be in reverse position.
• The wires may be broken.
• The wire in the wall OR the wall
control may be defective.
• The wires may be in reverse position.
• The push button may be defective.
• The circuit board may be defective.
• The motor may be defective.
• The motor capacitor may be defective.
• The motor is unplugged from inside
the unit.
• The motor is unplugged from the
electronic board (J4).
• There is a problem with the door
magnet switch.
• JU-1 jumper is missing or in wrong
position.
• Ice deposits may be hindering the
damper operation.
• The damper rod or the port damper
itself may be broken.
• The damper actuator or circuit board
may be defective.
• The 30-second boot sequence is not
completed.
• The circuit board may be defective.
• The transformer may be defective.
Y
OU SHOULD TRY THIS
• Ensure that the color coded wires have been connected to their appropriate
places.
• Inspect every wire and replace any that are damaged.
• Remove the wall control and test it right beside the unit using another shorter
wire. If the wall control works there, change the wire. If it does not, change the
wall control.
• Ensure that the color coded wires have been connected to their appropriate
places.
• Jump the OL and OC terminals. If the
unit switches to high speed, remove the
Dehumidistat or push button and test it right
beside the unit using another shorter wire. If
it works here, change the wire. If it doesn't,
change the Dehumidistat or the push button.
• Press on the integrated control push button until the unit turns on low speed
(the LED will light AMBER). Using a multimeter, check the voltage on J9-4 and
J9-3. Refer to Section 6 Wiring Diagram. The reading must be 120 VAC Then
set the unit on high speed by pressing on the integrated control push button one
more time (the LED will light GREEN). Using a multimeter, check the voltage
on J9-4 and J9-2. The reading must be 120 VAC Check also between J4-2 and
J4-1, the reading must be 120 VAC Refer to Section 6 Wiring Diagram. Check if
the fuse F1 is intact. If all the readings correspond to the right voltage values,
the circuit board is not defective. If one or both readings are different, change
the circuit board.
• Using a multimeter, check for 120 VAC for the following speeds: High Speed:
between GREY and ORANGE wires; Low/Medium Speed: between GREY
and RED/BLUE wires. Refer to Section 6 Wiring Diagram.
• Unplug the unit. Check for continuity between Pin 5 on the 6-pin connector
(brown leads) and Pin 3 of the capacitor connector. Also check for continuity
between Pin 4 on the 6-pin connector (brown leads) and Pin 1 of the capacitor
connector. Refer to Section 6 Wiring Diagram.
• Open the door and ensure that the wire going to the motor is connected.
• Check J4 motor connection on circuit board.
• Door magnet switch is missing or not in its place (see item no. 11 on page 18).
• Ensure JU-1 jumper is set on "M" speed (refer to Section 6 Wiring Diagram).
• Remove the ice.
• Inspect these parts and replace if necessary.
• See point 6.
• See Section 4.1.1 Boot Sequence (page 13).
• Check voltage going to circuit board J8-1 and J8-2.
• Check for 24 VAC on J8-1 and J8-2.