○ : interchangeable with current R22
× : Prohibited
Interchangeability
with R22
Measuring Instrument
and Tool
R407C
Pipe Cutter
Chamfering
Reamer
Flaring Tool
Extrusion -
Adjustment
Gauge
Pipe Bender
Refrige-
Expanding
rant
Tool
Pipe
Torque
Wrench
Brazing Tool
Nitrogen Gas
Lubrication Oil
(for Flare
Surface)
Refrigerant
Cylinder
Vacuum Pump
Adapter for
Vacuum
Interchangeable
PumpReverse
with R410A
Flow prevention
Refrige-
rant
Control Valve
Charge
Charging
Vacuum
Hose
Drying
Charging
Cylinder
Weight Scale
Refrigerant
Gas Leakage
Interchangeable
Detector
with R410A
※ interchangeable with R407C
2.Before Installation
Line-Up of Outdoor Unit
【Basic Unit】
Capacity
72(6RT)
kBtu/h(RT)
Model
AVWT-72FHFSHA
Capacity
192(16RT)
kBtu/h(RT)
AVWT-192FHFSHA
Model
R410A
R410A requires high pressure resistance piping and
*
○■
larger flaring. In case of material 1/2H, flaring is not
available.(The flaring tools for R410A are applicable to
R407C)
-
In case of material 1/2H, bending is not available. Use elbow
*
for bend and braze.
In case of material 1/2H, expanding of tube is not available.
*
Use joint for connecting tube.
For Φ1/2in., Φ5/8in. of R410A, spanner size is up to 5/64in.
*
For Φ1/4in.,Φ3/8.、Φ3/4in., spanner size is the same.
*
Perform brazing work properly (adjustable flame and heating
*
method, filler applicable)
Strict control against contamination (Blow nitrogen during
*
brazing.)
Use a synthetic oil which is equivalent to the oil used in the
*
refrigerant cycle.
Synthetic oil absorbs moisture quickly.
*
Check the cylinder for the corresponding refrigerant.
*
★Liquid refrigerant charging is required regarding zeotropic
refrigerant.
★The current pumps are applicable. However, it is required to
mount a vacuum pump adapter which can prevent reverse flow
※■
when a vacuum pump stops, resulting in no reverse oil flow.
No interchangeability is available due to higher pressures
*
when compared with R22. Connection diameter is different:
R410A: UNFl/2, R407C: UNF7/16
★Do not use old ones to the different refrigerant. Otherwise,
mineral oil will flow into the cycle and cause sludges, resulting
in clogging or compressor failure.
Use the weight scale when charging
*
×
×
The current gas leakage detector (R22) is not applicable due
※■
*
to different detecting method.
96(8RT)
AVWT-96FHFSHA
■: only for Refrigerant R410A (not interchangeable with R22)
● : only for Refrigerant R407C (not interchangeable with R22)
Reason of Non-Interchangeability
and Attention (★: Strictly Required)
——
——
120(10RT)
AVWT-120FHFSHA
2
Application
Cutting Pipe
Removing Burrs
Flaring for Tubes
Dimensional
Tube after Flaring
Bending
Expanding Tubes
Connection of Flare Nut
Brazing for Tubes
Prevention from Oxidation
during Brazing Air-tight test
Applying Oil to the Flared
Surface
Refrigerant Charging
Vacuum Pumping
Vacuum Pumping, Vacuum
Holding, Refrigerant Charg-
ing and Check of Pressures
Refrigerant Charging
Measure refrigerant quantity
Refrigerant Charging Gas
Leakage Check
144(12RT)
AVWT-144FHFSHA
AVWT-168FHFSHA
Control
of
168(14RT)