Setting of Refrigerant Cycle No.
In the same refrigerant cycle, set the refrigerant cycle No. for the outdoor units as shown below.
NOTE: In the same refrigerant cycle, set the same refrigerant cycle No. for the outdoor unit and the indoor unit.
10 digit
ON
OFF
1 2 3 4 5 6
Outdoor Unit
DSW1
Ex: In Case of Setting Refrigerant Cycle No. 25
ON
OFF
OFF
5 6
1 2 3 4
Turn ON No. 2 pins
Turn ON No. 1 and No. 3 pins
(The settings in binary system shall be
only valid for 0~9 and it will alarm once
exceeding.)
DSW1 and DSW8 setting before shipment is 0.
Maximum in setting refrigerant cycle No. is 63.
Setting of Terminal Resistance
Before shipment, No.1 pin of DSW10 is set at the "ON"side. In
the case that the outdoor units quantity in the same H-NET is
2 or more, set No. 1 pin of DSW10 at the "OFF" side from the
2nd refrigerant group outdoor unit. If only one outdoor unit is
used, no setting is required.
Outdoor Unit
DSW10
1 2
Communication cable
(H-NET)
Indoor
Unit
Setting Switch
1 digit
ON
OFF
1 2 3 4
DSW8
1 2 3 4
Set Position 1 on DSW10 to
OFF to cancel setting of
terminal resistance.
Outdoor Unit
DSW10
DSW10
Outdoor
Outdoor
1 2
Outdo or
1 2
Unit A
Unit B
(Main)
(Sub)
Communication cable
(H-NET)
Indoor
Unit
0~9 Binary System Dip Setting Method for DSW8
0
1
2
3
4
DSW10
ON
OFF
1 2
Outdoor Unit
DSW10
DSW10
Outdoor
1 2
1 2
Unit A
Unit C
(Sub)
(Main)
Communication cable
Indoor
Unit
26
ON
OFF
5
1 2 3 4
ON
OFF
6
1 2 3 4
ON
OFF
7
1 2 3 4
ON
OFF
8
1 2 3 4
ON
OFF
9
1 2 3 4
Setting of Terminal Resistance
DSW10
Before Shipment
Cancellation
ON
OFF
1
2
1
2
Set Position 1 on DSW10 to
OFF to cancel setting of
terminal resistance.
Outdoor Unit
DSW10
Outdoor
1 2
Unit B
(Sub)
(H-NET)
Indoor
Unit
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
DSW10
ON
OFF
1 2
DSW10
1 2