5.2 Connection of the power supply
The pump must be protected on-site (min. 10 A, slow) and must be connected to an external
mains switch. All cables used must have a heat resistance of up to 85 °C.
They must not be in contact with the pipe or the pump and motor casing.
All cables must be connected in accordance with EN 60204-1 and EN 50174-2: 2000.
The electrical connection must be made as indicated on the nameplate.
ModulA...
ModulA 32F-12 220, ModulA-D 32F-12 220
ModulA 40-8 220, ModulA-D 40-8 220
ModulA 40-10 220, ModulA-D 40-10 220
ModulA 40-12 250, ModulA-D 40-12 250
ModulA 40-18 250, ModulA-D 40-18 250
ModulA 50-6 240, ModulA-D 50-6 240
ModulA 50-6 270
ModulA 50-8 240, ModulA-D 50-8 240
ModulA 50-12 270, ModulA-D 50-12 270
ModulA 50-18 270, ModulA-D 50-18 270
ModulA 65-8 270
ModulA 65-8 340, ModulA-D 65-8 340
ModulA 65-12 340, ModulA-D 65-12 340
ModulA 65-15 340, ModulA-D 65-15 340
ModulA 80-8 360, ModulA-D 80-8 360
ModulA 80-12 360, ModulA-D 80-12 360
ModulA 100-12 450, ModulA-D 100-12 450
L
N
Example of a typical mains connection, 1x230V ±10%, 50 / 60Hz
Legende:
1 Sicherung (min.10A, träge)
2 Externer Schalter
Protection
1
(minimum 10A,
inert)
FI
Nennstrom [A]
0.17 – 1.50
0.20 – 1.21
0.19 – 1.54
0.18 – 1.91
0.18 – 2.63
0.21 – 1.09
0.21 – 1.09
0.21 – 1.42
0.21 – 2.32
0.21 – 3.34
0.24 – 2.10
0.24 – 2.10
0.22 – 3.32
0.28 – 5.68
0.29 – 3.08
0.32 – 5.56
0.32 – 6.78
external
2
switch
Leistung P
[W]
1
16 – 328
20 – 268
18 – 341
17 – 421
16 – 594
21 – 236
21 – 236
22 – 315
20 – 516
22 – 742
22 – 464
22 – 464
21 – 736
30 – 1254
29 – 704
32 – 1282
35 – 1563
961613_02