Descargar Imprimir esta página

Vortice 12101 Manual De Instrucciones página 30

Ocultar thumbs Ver también para 12101:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 96
ENGLISH
5
Connecting the condensate drain tube
The connection point is located on the bottom of the device. The condensate drain must be implemented by connecting the
supplied flexible hose to the condensate drain connection. A siphon must be made with the tube (Fig. 6,7) to prevent the
formation of air bubbles.
6
Piping connection
(fig.8)
The device fittings have a nominal diameter of 160 mm. Rigid or flexible
pipes can be connected to the device inlets. Below is an illustration of each
connection with a specification also of the directions of origin and supply of
the relative air flow.
ATTENTION: For passivhaus compliant systems, it will be necessary to
install silencers on all 4 air vents.
30
5a
5a
7
h > 50 mm
≥ 60 mm

Publicidad

loading

Este manual también es adecuado para:

Vort hr 450 avel d hVort hr 450 avel d