This is the variable that defines the possible strategies for NO FROST operation. The possible values are:
UN-BALAN.: flow unbalancing; note: this option must be deactivated in order for the appliance to comply with standard
PASSIVHAUS and preheater installed.
HEATER: pre-heater; note: this option must be activated in order for the appliance to comply with standard PASSIVHAUS.
HEAT FORC.: in the case that the pre-heater strategy is activated, this permits the installer to control pre-heater operation,
switching it on for 15 s
Pre-set default values :
UN-BALAN: Not enabled
HEATER: Not enabled
INSTALL
NO FROST
POSTHEAT
POSTTEMP
POSTHEAT
The variable that controls activation of the post-heater, if present. The editable default value is: NO.
INSTALL
NO FROST
POSTHEAT
POSTTEMP
POSTTEMP
The variable that defines the threshold temperature value, over which the post-heater switches on, if present. The editable
default value is: 16°C.
INSTALL
NO FROST
POSTHEAT
POSTTEMP
NOFROST
UN-BALAN.
HEATER
HEAT  FORC.
POSTHEAT
YES
POSTHEAT
16
41