Descargar Imprimir esta página

Webasto ProCore Edge 30 Guia De Instalacion página 10

Ocultar thumbs Ver también para ProCore Edge 30:

Publicidad

Idiomas disponibles

Idiomas disponibles

ProCore Edge 30 North America
2.
Connect an NEC-approved AC shielded input cable (such as type SOOW) or conduit to the
charger through the AC service entrance (Figures 11-13), which is the hole located in the top
left corner of the charger. (The AC service entrance provides two hole sizes.)
Use the appropriate minimum wire size (gauge) or larger for the maximum kilowatt rating of the
charger. See section 2 for the minimum fitted AC input wire size (AWG) per NEC.
Figure 11 – AC
Service Entrance
Figure 12 – AC Service Entrance
Torque Specifications Label
DANGER
RISK OF ELECTRIC SHOCK
Special Note:
power cable. If the AC cable is to be disconnected during service, the longer earth wire
should be the last wire to be disconnected to prevent electric shock.
NOTE
The 10-bay cabinet has field wiring terminal blocks that can accept a wire gauge range
from #10 AWG to #4 AWG. As shown on the previous page, the minimum and maxi-
mum screw-tightening torque is 23 in-lb (2.6 Nm) and 26 in-lb (2.9 Nm) respectively.
3.
Use the provided round panel to use the smaller hole size, or remove the panel to use the
larger hole size.
4.
Place an appropriate cable gland or conduit clamp in the AC service entrance hole to secure
the cable or conduit.
5.
Connect the three-phase AC input power cables.
5912526 A01
Be sure the earth (ground) wire is longer than the other wires on the AC
Page 10 of 12
FACING THE AC
SERVICE ENTRANCE
Ground & Power Cables
TOP VIEW
Webasto Charging Systems, Inc.
Installation Guide
DIRECTLY
L1
L2
L3

Publicidad