WEG CFW700 Serie Manual Del Usuario página 39

Ocultar thumbs Ver también para CFW700 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Keypad (HMI) and Basic Programming
P1012 - PID Process Variable
Adjustable
0.0 to 3000.0
Range:
Properties:
ro
Access Groups
SPLC
via HMI:
Description:
Read only parameter that presents, in the wxy.z form without engineering unit, the value of
the process variable of the PID Controller according to the scale defined at P1018.
P1013 - PID Controller Output
Adjustable
0.0 to 100.0 %
Range:
Properties:
ro
Access Groups
SPLC
via HMI:
Description:
Read only parameter that presents, in percentage (%), the PID Controller output value.
P1016 - PID Controller Setpoint Selection
Adjustable
0 = HMI
Range:
1 = AIx
2 = Serial/USB
3 = CO/DN/DP
Properties:
ro
Access Groups
SPLC
via HMI:
Description:
It defines the origin source of the control setpoint of the PID Controller.
Notes:
"HMI" means that the control setpoint of the PID Controller will be the the value of of P1025
parameter.
"AI" means that the control setpoint of the PID Controller will come from an analog input. It
is necessary to set P0231 (AI1) or P0236 (AI2) to 5 = Function 1 of the Application in order to
enable its operation. The following alarm message will be displayed in case it is not properly
done: "A0770: Set AI1 or AI2 for Function 1 of the Application".
"Serial/USB" means that the control setpoint of the PID Controller will be the value of P0683
proportionally referenced to the percentage value with one decimal point, i.e., 100.0 %
corresponds to 1000 in P0683.
34 | CFW700
Factory
-
Setting:
Factory
-
Setting:
Factory
0
Setting:

Publicidad

Tabla de contenido
loading

Tabla de contenido