Keypad (HMI) and Basic Programming
Definition:
The Function 1 of the Application in the parameters P0266 to P0268 represents the Multispeed
command.
The speed reference selection works according to the table below:
DI6
0 V
0 V
0 V
0 V
24 V
24 V
24 V
24 V
If any digital input is selected for Multispeed, it should be considered as 0 V.
The parameters P1011 to P1018 define the speed reference value when the Multispeed is
operating.
P1010 - Version of the Multispeed Application
Adjustable
0.00 to 10.00
Range:
Properties:
ro
Access Groups
SPLC
via HMI:
Description:
Read only parameter that presents the software version of the Multispeed application
developed for the SoftPLC function of the CFW700.
P1011 - Multispeed Reference 1
Adjustable
0 to 18000 rpm
Range:
Properties:
ro
Access Groups
SPLC
via HMI:
Description:
Sets the speed reference 1 for the Multispeed application.
42 | CFW700
Table 4.3: Multispeed Reference
DI5
DI4
0 V
0 V
0 V
24 V
24 V
0 V
24 V
24 V
0 V
0 V
0 V
24 V
24 V
0 V
24 V
24 V
Speed Reference
P1011
P1012
P1013
P1014
P1015
P1016
P1017
P1018
Factory
Setting:
Factory
Setting:
-
90 rpm