4.4 Adjustment of cable length for a
float switch
The difference in level between start and stop
can be adjusted by changing the free cable
length between the float switch and the pump
handle.
•
An increased free cable length will result in
fewer starts and stops and a large difference
in level.
•
A reduced free cable length will result in
more frequent starts and stops and a small
difference in level.
The free cable length must be:
•
at least 2.5 in. (63.5 mm)
•
no more than 6 in. (152 mm)
Minimum and maximum cable length
• • • • • • • •
• • • • • • • •
• • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • • •
•• • • • • • • • • • • • •
Fig. 5
Start and stop levels
The start and stop levels vary according to the
cable length.
Unilift KP start and stop levels
Cable length min.
2.5 in. (63.5 mm)
Pump
type
Start
Stop
KP
150
11.5 in.
5.5 in.
(292 mm)
(140 mm)
KP
250
KP
12 in.
6 in.
350
(305 mm)
(152 mm)
Manual operation can be achieved in one of two
ways:
•
Unplug both the pump and float switch from
the wall socket. Insert the pump plug into the
wall socket.
•
Keep the float switch in a high position by
attaching it to the outlet pipe or hose.
Start
Stop
Cable length max.
6 in. (152 mm)
Start
Stop
12.5 in.
3.5 in.
(318 mm)
(89 mm)
13 in.
4 in.
(330 mm)
(102 mm)
4.5 Check valve
Whenever the pump is installed in a permanent
installation with a float switch, a check valve
must be fitted in the outlet pipe or hose.
4.6 Electrical connection
DANGER
Electric shock
Death or serious personal injury
- Pump installation in a sump pit,
basin or tank must be carried out
by qualified, specially trained
persons in accordance with the
National Electrical Code and any
state, local governing codes and
regulations.
WARNING
Electric shock
Death or serious personal injury
- Connect the product only to a
properly grounded receptacle.
- We recommend that you connect
the pump to an electrical circuit
with a Ground Fault Circuit
Interrupter (GFCI).
WARNING
Electric shock
Death or serious personal injury
- The protective ground of the pump
power plug must be connected to
the protective ground receptacle of
the power outlet.
- The plug must have the same
ground connection system as that
of the power outlet. If not, use a
suitable adapter.
The electrical connection must be carried out in
accordance with local regulations and follow the
National Electrical Code (USA) and the
Canadian Electrical Code. The pump must be
grounded. The operating voltage and frequency
are marked on the nameplate. Make sure that
the motor is suitable for the power supply on
which it will be used.
9