INSTALLATION
Dimensions
Dimensions
Dimensions
Item
in (mm)
1
8 (203.2)
2
7 (177.8)
3
5.72 (1452)
4
3.45 (87.7)
5
10.43 (265)
6
9.31 (236.4)
7
6.65 (168.9)
8
2.92 (74.1)
9
1.50 (38.1)
10
18.84 (478.5)
11
17.32 (439.9)
Electrical Installation
Risk of severe injury or death by electrical shock.
Always disconnect the electrical power before working on or around the system.
Capacitors inside the drive can still hold lethal voltage even after power has been disconnected.
Allow 5 minutes for dangerous internal voltage to discharge before removing cover.
Employ a licensed electrician.
Over
Temp.
Switch
Pressure
Sensor
Green
Incoming
Black
Red
Power
1.
Disconnect electrical power at the main breaker.
2. Connect the pump to its own circuit, with no other electric receptacles or equipment in the circuit.
3. Check that the power supply corresponds with the electrical rating of the pump being installed.
Supply voltage must be
4. Connect to a circuit equipped with a ground fault circuit interrupter (GFCI) device if required by code.
5. Pull black, red, and green (ground) wires though Listed liquid-tight conduit to connect directly to a
dedicated mains circuit junction box or panel with 15A Listed fuses or 15A Listed circuit breaker.
6. Connect wire assembly to the pump per
NOTE: Wire liquid-tight conduit, assembly, and all connections to comply with local codes.
8
1
3
2
Connection between the two PCB assemblies
Power Supply
PCB Assembly
±
10% of the nameplate voltage (230 V).
"Power Wiring Connections" on page
5
4
10
11
Red
Black
Motor
Yellow
Green
Control PCB Assembly
9.
9
6
7
8