Pressing the UP button 6 times displays CNT (counter)
Press the OK button, the display shows the letter A (absolute counter cannot be reset) the number that follows should be multiplied by 10000
Press the DOWN button, the display shows the number to be added to get the total openings performed by the motor: absolute number =
(000*10000)+(7000)= 7000
Press the DOWN button, the display shows the letter P (partial counter can be reset) the number that follows should be multiplied by 10000
Press the DOWN button, the display shows the number to be added to get the openings after resetting the partial counter: partial
number = (000*10000)+(1000)= 1000, this means that it was reset on 6000 openings. To reset the partial counter, press
and hold down the OK button for at least 5 seconds.
7.7- ERR:
Shows the last 9 faults or errors: when the gate is not moving, you can view the last fault during operation.
Pressing the UP button 7 times displays Err (list of faults or errors)
Press the OK button, the display shows the letter 1.F Xx, the first digit indicates the progressive error log number, ranging from 1 to 9, the highest value indi-
cates the most recent error, xx indicates the type of error, see the errors table:
To clear the error list: enter the ERR menu and hold down the OK button for at least 5 seconds.
Display message
Description
no
No alarm saved in the location
F01
Detected a problem on the output powering the motor M1
F02
Detected a problem on the output powering the motor M2
F03
Detected an obstacle during the opening movement of motor M1
F04
Detected an obstacle during the opening movement of motor M2
F05
Detected an obstacle during the closing movement of motor M1
F06
Detected an obstacle during the closing movement of motor M2
F07
Not used
F08
Not used
F09
Not used
F10
External memory damaged
F11
Exceeded the maximum time during the calibration phase
F12
Fuse damaged or blown
F13
Occurs when the time out is exceeded during the travel
F14
Error when reading encoder M1
F15
Error when reading encoder M2
F16
Detected too high current absorption on the motor M1 power output
F17
Detected too high current absorption on the motor M2 power output
7.8 - PASS:
you can enable a password with 3 levels, with level 1 password is required to enter the menu PAR, DEF, and LRNE LRN, with level 2 password
is required to enter the menu RAD, with level 3 password is required to enter all the menu items (LRNE, LRN, DEF, RAD, CNT, PAR ERR).
NB: In case you lost your password you need to call the service center
Example of entering the password 4-3-2-1 on the second level:
x4
x4
x4
If you enter the password to level 1-2 or 3 when you select the menu item will be prompted for the password-protected, enter the password and
confirm with OK, if you exit the menu will be prompted for the password.
If the password is incorrect in the display shows NO.
36
x7
x2
x3
x3
x2
x2
x1
x1
EN