Delete the time scale in one day.
1
Confirm
2
Confirm
-
+
3
Day off/Del
-
+
Press + and − to select the setting time want to delete. The setting time,
mode, temperature and fan speed appear on the LCD. The setting time,
mode, temperature and fan speed can be deleted by pressing the DEL
(day off ).
11. Fault alarm handing
If the system does not properly operate except the above mentioned cases or the
above mentioned malfunctions is evident, investigate the system according to the
Wired controller error codes
Nº
Code
1
F0
Error of communication between wire controller and indoor unit
2
F1
The lifting filter function is abnormal
3
F2
The air inlet grill doesn't fit well of Super slim four-way cassette
4
E0
Error of power supply phase sequence
5
E1
Error of communication between indoor unit and outdoor unit
6
E2
T1 temp. sensor is abnormal
7
E3
T2A temp. sensor is abnormal
8
E4
T2B temp. sensor is abnormal
9
E5
T3/T4 temp. sensor is abnormal or compressor discharge temp. sensor is abnormal
10
E6
Zero crossing detection error
11
E7
EEPROM malfunction
12
E8
Fan speed out of control
13
E9
The communication between main board and the display board is abnormal
14
EA Compressor over current protection (four times)
15
EB IPM malfunction
16
ED Outdoor unit malfunction
17
EE
Water-level alarm and other malfunction
18
EF
Other malfunction
Please check the error display of indoor unit and read <<OWNER'S MANUAL>>
if other error code appears.
12. Technical indication and requirement
EMC and EMI comply with the CE certification requirements.
Note:
The design and specifications are subject to change without prior notice for product
improvement. Consult with the sales agency or manufacturer for details