Descargar Imprimir esta página

mundoclima MUCR-H11 Serie Manual De Instalación Y Usuario página 75

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.
Precautions
Execute heat insulation work completely on both sides of the
gas piping and liquid piping. Otherwise, this can sometimes
result in water leakage.
(When using a heat pump, the temperature of the gas piping can
reach up to approximately 120 . Use insulation which is
sufficiently resistant.)
Also, in cases where the temperature and humidity of the
refrigerant piping sections might exceed 30
reinforce the refrigerant insulation(20mm or thicker).
Condensation may form on the surface of the insulating material.
Before rigging tubes, check which type of refrigerant is used.
Use a pipe cutter and flare suitable for used refrigerant.
Only use annealed material for flare connections.
Do not mix anything other than the specified refrigerant, such
as air, etc.., Inside the refrigerant circuit.
If the refrigerant gas leaks during the work, ventilate the area.
A toxic gas is emitted by the refrigerant gas being exposed to
a fire.
Make sure there is no refrigerant gas leak. A toxic gas may be
released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.
Refer to the table below for the dimensions of flare nuts spaces
and the appropriate tightening torque. (Over tightening may
damage the flare and cause leaks.)
Pipe gauge
Tightening torque
(mm)
15~16 N. m
O6.35
(153~163 kgf.cm)
25~26 N. m
O9.52
(255~265 kgf.cm)
35~36 N. m
O12.7
(357~367 kgf.cm)
45~47 N. m
O15.9
(459~480 kgf.cm)
97.2~118.6 N. m
O19.1
(990~1210 kgf.cm)
Check whether the height drop between the indoor unit and
outdoor unit, and the length of refrigerant pipe meet the following
requirements:
Pipe
Max. Lenght (m)
Model
Gas
Liquid
A (Vertical)
12
3/8"
1/4"
10
18
1/2"
1/4"
20
24
5/8"
3/8"
25
30
5/8"
3/8"
25
36
5/8"
3/8"
30
42
5/8"
3/8"
30
48
5/8"
3/8"
30
60
5/8"
3/8"
30
The minimum pipe length is 3m.
or Rh80%,
Flare dimension
Flare shape
A (mm)
8.3~8.7
o
4
90
o
12.0~12.4
A
15.4~15.8
R0.4~0.8
18.6~19.0
22.9~23.3
Aditional
Preload up
refrigerant
B (Total)
charge (g/m)
25
12
30
12
50
24
50
24
75
24
75
24
75
24
75
24
Oil traps
If oil flows back into the outdoor unit's compressor, this
might cause liquid compression or deterioration of oil
return. Oil traps in the rising gas piping can prevent this.
-An oil trap should be installed every 6m of vertical
suction line riser 6m (models 12K~30K)
-An oil trap should be installed every 10m of
vertical suction line riser 10m (models 36K~60K)
Oil trap
IDU
or
ODU
3.1 Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward so that the
chips do not enter the pipe.
Cut exactly at
right angles.
3) Put the flare nut on the pipe.
4) Flare the pipe.
A(mm)
Outer diam.
to
(mm)
Max.
(m)
1.3
O6.35
5
5
O9.52
1.6
5
O12.7
1.8
5
5
O15.9
2.2
5
5
5
75
Gas
IDU
or
ODU
6m (models 12K~30K)
10m (models 36K~60K)
Liquid
6m (models 12K~30K)
10m (models 36K~60K)
Remove burrs.
Set exactly at the position shown below.
Min.
0.7
1.0
1.0
Copper pipe
2.0
A: Vertical
B: Total
Die

Publicidad

loading