OPTION 2:
Automatically using the "AF" function of the KJR-120G2 in the wired remote control.
Please, follow the steps:
1. Make sure that the evaporator battery of the indoor unit is completely dry. If it isn't turn on the equipment
in VENTILATION mode for at least 2 hours to dry the battery.
2. Ensure that all ductwork is complete, that all grilles or gates are open and that the air filter is correctly installed in the return
circuit of the equipment.
3. If there are several air inlets and outlets, adjust the gates so that the airflow of each inlet and outlet meets the airflow rate
designed. Make sure the unit is in VENTILATION mode. Press the air speed setting button to change the High (H) or Low (L)
speed on the wired remote control.
4. Adjust the parameters for the automatic adjustment of the air flow. While the device is stalled, perform the following steps:
- Press the "COPY" button for 3 seconds.
Copy/
Follow me
- Press the "+" or "-" button until "AF" is selected.
-
+
- Press the "CONFIRM" button. The unit will automatically start the air flow rate.
While the automatic airflow setting mode
Confirm
is active, it will turn "ON" on the remote
control.
After 3 or 6 minutes, the unit will stop automatically following the completion of the automatic adjustment mode.
5.
WARNING:
- Never modify the gates or grilles while the automatic airflow adjustment mode is active.
- If there is no change in the air vents after the automatic adjustment, be sure to restore the automatic airflow adjustment.
- If there is no change in the ventilation channels after the automatic adjustment, contact your supplier, especially if this happens after
testing the outdoor unit or if the unit has been moved from one place to another.
- Do not perform automatic adjustment of airflow if fans, air treatment units or air drawers are installed in the same duct as the air
conditioner.
- If the duct has been modified, you must reset the duct by performing a new adjustment from point 3.
External static pressure curves
MUCR-12-H11-I
Air flow (m3/h)
(without filter)
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
10
20
SP3-L
SP1-M
SP1-L
SP2-L
25
30
40
SP1 (Setting 1)
SP2 (Setting 2)
SP3 (Setting 3)
SP4 (Setting 4)
SP4-H
SP3-H
SP4-M
SP2-H
SP3-M
SP1-H
SP4-L
SP2-M
External static pressure (Pa)
50
67