5.8
Environmental influences
Ambient temperature range
Storage
Operation
Site altitude
Climatic environmental influences
Resistance to climatic conditions ≤ 90 % rel. humidity without condensation
Storage
Operation
Vibration
Amplitude
Acceleration
Shock
Peak acceleration
Shock duration
Electromagnetic compatibility
(EMC)
Interference emission
Interference immunity
a
The product is suitable for industrial use as well as for households and small businesses.
b
With Ethernet interface: Class A – only for industrial use –
5.9
Case
Case type
Case front
Panel thickness
Case mounting
Operating position
Protection type
Weight
Type 703051 (format 116)
Type 703052 (format 108H)
Type 703053 (format 108Q)
Type 703054 (format 104)
a
The maximum admissible ambient temperature only applies for the installation with the display in a vertical position.
-30 to +70 °C
-10 to +55 °C
Max. 2000 m above sea level
According to DIN EN 60721-3 with extended temperature range
According to class 1K2
According to class 3K3
According to DIN EN 60068-2-6, table C.2
0.15 mm from 10 to 58.1 Hz
2
20 m/s
from 58.1 to 150 Hz
According to DIN EN 60068-2-27, table A.1
2
150 m/s
11 ms
According to DIN EN 61326-1:2013
a, b
Class B
Industrial requirements
Plastic case for panel mounting according to DIN IEC 61554 (indoor use)
Made of plastic with membrane keyboard
1 to 10 mm
In panel using the supplied mounting frame or both mounting elements
a
Any
According to DIN EN 60529, IP65 on the front, IP20 on the back
Max. 170 g
Max. 271 g
Max. 271 g
Max. 417 g
5 Technical data