IMPORTANT NOTES
1) Do not glue the pipes into the inlets or outlets of the
FAAST LT-200 unit. Devices with glued pipes will be deemed as
out of warranty because they cannot be tested.
2) It is recommended that the inlet and outlet connections remain
plugged prior to use, and the outlet is temporarily sealed if the
device is turned off during maintenance periods to prevent ingress
of insects and spiders.
WIRING INSTALLATION
Power, Alarm and Control Connections
EARTH BAR
MOUNT
F-LT-EB
EARTH BAR
(OPTIONAL)
POWER AND
ALARM
CONNECTIONS
EARTH BAR
MOUNT
MODULE MOUNT
F-LT-PMB
MODULE MOUNT
KIT (OPTIONAL)*
MODULE MOUNT
*If
required,
an
input/output
module can be installed into the
FAAST LT-200 unit. The optional
module mount kit (F-LT-PMB) will be
needed for this.
N200-102-01
4
6
CHANNEL 1 FILTER
CHANNEL 2 FILTER
PLACE
WIRING
LABEL
HERE
USB PORT
SENSOR COVER
POSITION FOR
TEST MAGNET
Exhaust Pipe
Whenever the FAAST LT-200 is installed outside the risk area, return
of the exhaust air back into the protected area can reduce flow faults
due to pressure difference.
P P
P
!
If the FAAST LT-200 door is closed for a long
time (especially at high temperatures) it may
be necessary to use a flat-bladed screwdriver
between the two tabs at the top of the unit to
lever open the door (as shown above).
Figure 9: Inside the Detector
Note 1: All wiring should comply with local
requirements and regulations.
Note 2: Panel wiring must observe the
recommendations of the panel manufacturer
4
SAMPLING AREA
SAMPLING AREA
I56-6577-008