Descargar Imprimir esta página

Siemens SIMATIC S7-300 Información Del Producto página 7

Produktinformation snmp deaktivieren
Ocultar thumbs Ver también para SIMATIC S7-300:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 16
ET 200pro
IM154-8 PN/DP CPU
IM154-8F PN/DP CPU
IM154-8FX PN/DP CPU
Deactivating/activating SNMP
Under certain conditions, it is useful to deactivate SNMP. Examples:
● The security guidelines in your network do not allow the use of SNMP.
● You use your own SNMP solution, e.g. with your own communications instructions.
If you deactivate SNMP for a device, various options for diagnostics of the network topology (e.g. using the PRONETA tool
or the Web server of the CPU) are no longer available to you.
To deactivate/activate SNMP for the integrated interfaces of the CPU, follow these steps:
1. In STEP 7, create a data block that contains the structure of data record B071
The following table shows the structure of the data record B071
Byte
Element
0 to 1
BlockID
2 to 3
BlockLength
4
Version
5
Subversion
6 to 7
Reserved
8 to 11
SNMP controller
2. Transfer the data record B071
Use the diagnostics address of an integrated interface of the CPU here.
Product information Deactivating SNMP
A5E46739177-AA, 02/2019
6ES7 154-8AB01-0AB0
6ES7 154-8FB01-0AB0
6ES7 154-8FX00-0AB0
Code
F003
H
8
01
H
00
H
-
Deactivation/activation of
SNMP
in the startup OB (OB100) with the WRREC instruction (write data record) to the CPU.
H
V3.2.16 or higher
V3.2.16 or higher
V3.2.16 or higher
.
H
.
H
Explanation
Header
The data record length is counted starting at byte 4
"Version".
-
If you want to deactivate SNMP, enter the value 0.
(16#0000_0000)
If you want to activate SNMP, enter the value 1.
(16#0000_0001)
7

Publicidad

loading

Este manual también es adecuado para:

Simatic et 200sSimatic et 200pro