English
A5E41143091-AC
terminal assignment can be found in the "SIMATIC
Distributed I/O ET 200iSP" manual.
• The safety data (maximum values) for the
sensors/actuators must be adjusted to the electronic
submodule's corresponding maximum values. The
maximum values of the sensors/actuators can be found in
the associated ex certificates. In accordance with EN
60079-14, the following applies:
U
≤ U
; I
≤ I
; P
≤ P
; C
≥ C
+ C
; L
0
i
0
i
0
i
0
i
Line
Assembly
• Check the electronic submodule for damage. Only connect
undamaged electronic submodules to the terminal module.
• The first time that an electronic submodule is inserted, the
coding element on the terminal submodule will snap in,
which prevents the insertion of an incorrect submodule.
This mechanical coding may not be changed.
English
≥ L
+ L
0
i
Line