Before starting up, read this Manual thoroughly and follow the instructions to avoid any
wrong settings and operations that could cause operating faults.
-
Do not start the pumps dry, not even for a few moments.
-
The inverter can be switched on only after performing all the steps described in the
INSTALLATION chapter
-
When DGFIT is powered by the mains, it enters a STARTING phase, followed by a prompt
to reset the parameters, in self-learning by WIZARD; these phases last about 10 seconds,
after which the inverter returns to the same operating conditions in which it was upon the
last shutdown:
o IN SERVICE if on the last shutdown it was IN SERVICE
o OUT OF SERVICE if on the last shutdown it was OUT OF SERVICE (OFF)
In the event of an accidental voltage drop, if DGFIT was IN SERVICE (ON), when network
is restored it returns automatically INTO SERVICE (ON).
-
To PUT DGFIT INTO SERVICE / OUT OF SERVICE , press the START/STOP key.
-
In applications with inverters in parallel (MASTER / SLAVE) only the MASTER inverter
receives the input from the keypad
-
SLAVE inverters operate autonomously only if the MASTER is off; in this case they
receive inputs from their own keypad.
-
In each unit there can be only one MASTER, one SLAVE 1 and one SLAVE 2.
-
In normal operation it is possible to view the status parameters.
To view the operation parameters see
keypad
FIRST START-UP
QUICK INSTRUCTIONS .
LIGHT SIGNALLING
ON
OFF
POWER
DGFIT does not detect any power supply.
STATUS
ATTENTION: the absence of power supply is
not guaranteed, the board may be faulty but
under tension.
POWER
DGFIT is powered up, but the pump is not
STATUS
running (STAND-BY)
POWER
DGFIT is powered up and the pump is running
STATUS
(STAND-BY)
POWER
DGFIT is powered up, but OUT OF SERVICE or
STATUS
under TEST; restoration is only manual
POWER
DGFIT is in alarm, restoration is only manual
STATUS
42
).
FLASHING
ST
PO