L2 WIFI WATER SENSOR AND SWITCH
1
2
Fig. 10. L2 locks out HM750 steam humidifier when water leak is detected.
TEST MODE
In test mode, alarm will sound and switches will change
position as described below.
Enter Test Mode
Press the sensor button three times until the LED blinks red.
To exit test mode and return to normal function, press the
Sensor button 3 more times. The L2 will also exit test mode by
itself after 30 minutes.
This feature will not function during
• An active alarm.
• A Firmware update (white light blinking).
33-00631EFS—02
HM750
Air proving
Humidistat
L1
(hot)
R
24 VAC
L2
C
24 volt transformer
See HM750 humidifier install guide for humidistat wiring.
If an optional sail switch or current sensing relay is not used, the green wire from
the L2 goes directly to the upper ap terminal at the HM750 humidifier.
Transformer
R
L1
24 VAC
120 VAC
L2
C
1
Line voltage wiring (including ground wire not shown) must meet local code.
2
A 24 vac transformer and relay are needed when controlling a line voltage
load with an L2. Resideo offers single-pole and double-pole R8222 relays.
Verify switch rating meets load of line voltage device.
3
If line voltage device should be deenergized when water leak is detected
and energized when a water leak is not detected, use 2 on a SPDT relay
rather than 3.
Fig. 11. L2 controlling a line voltage load.
1
Ap
Ap
Optional sail switch or
24 VAC
Current sensing relay
Com
Hum
Hum
Green
Orange
Red
Black
1
1
Relay
2
2
3
3
White
Green
Red
Black
6
2
White (not used)
L2
MCR39162
Line
voltage
load
Orange
(not used)
L2
MCR39384
3x
M39152
Fig. 12.