Descargar Imprimir esta página

Vortice VORT INVISIBLE MINI Manual De Instrucciones página 40

Ocultar thumbs Ver también para VORT INVISIBLE MINI:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 123
ENGLISH
7
1
8
Electrical connections
e
ATTENTION:
- This unit must have an earthing connection. All wiring must be compliant with the regulations in force
in the country of installation.
- The unit is compatible for a single-phase 220-240 V, 50 Hz power supply.
- The unit requires a flexible power cable. Connect the cable to the terminal block and let it out through
a cable gland and a cable clamp.
- The unit must be connected directly to the power supply through a special magnetothermal switch.
- To connect the HMI remote display to the machine, use cables with a section between 0.35 mm
and 2.5 mm
or away from the power cables, if there are problems of electromagnetic interference from other
devices installed in the environment (which produce malfunction of the display), it is recommended
to use shielded cables.
- To connect the product power supply, use a cable with a minimum section of 3X0.75 mm
9
40
2
. Max length 100 m. Given that the display connection cable should be kept separate
2
8
h > 50 mm
≥ 60 mm
2
H05VV-F.
2
LN

Publicidad

loading

Este manual también es adecuado para:

Vort invisible mini evoVort invisible mini top