• Register 13: Confi guration of CO
− 0: Without CO
2
Temperature probes supplied with CAD-REG
1: Without CO
EN
2
Temperature probes integrated in CAD-COMPACT
2: CO
sensor 0-10V 0-2000ppm.
2
Temperature probes supplied with CAD-REG
3: CO
sensor 0-10V 0-2000ppm.
2
Temperature probes integrated in CAD-COMPACT
4: AIRSENS CO
Temperature probes supplied with CAD-REG
5: AIRSENS CO
Temperature probes integrated in CAD-COMPACT
Default value: 0 [Without CO
• Register 14: CO
2
− The value that is sent is the value of the setpoint (400ppm to 1400ppm) in 16-bit binary.
Default value: 800 [800ppm].
• Register 15: Proportional band CO2 air quality [read/write].
− The value that is sent is the value of the proportional band (100ppm to 600ppm) in 16-bit binary.
Default value: 400 [400ppm].
• Register 16: Operating hours fi lters [read/write]. Only allowed write value: 0 (reset).
− The value that is sent is the value of the hours (0h to 65000h. The value of 65000h does not overfl ow) in 16-bit binary.
Default value: 0 [0h].
Note: The fi lter operating time is only increased if the fans are running.(Register 26 ≠ 0).
• Register 17: Differential pressure switch / s contact status for indication of dirty fi lter/s (digital input) [read/write].
0: Normally open contact (dirty fi lter / s at contact closure).
1: Normally closed contact (dirty fi lter (s) at contact opening).
Default value: 0 [Normally open contact (dirty fi lter / s at contact closure)].
Contacto normalmente abierto
Contact normally open (dirty fi lter/s at contact closure)
40
air quality sensor and temperature probes .
2
sensor.
sensor.
sensor.
2
sensor.
2
sensor / Temperature probes supplied with CAD-REG]
2
air quality setpoint [read/write].
Current speed fans (%)
Register 26
100%
Maximum speed (%)
Register 12
Speed (%)
Register 10
Minimum speed (%)
Register 11
0%
(filtro/s sucio/s al cierre del contacto)
Conexión presostato/s diferencial/es (entrada digital)
Differential/s pressure switch connection (digital input)
Proportional band (ppm)
Register 15
Register 29 (BIT4) = 0
Quality air setpoint (ppm)
Register 14
CO
Air quality function CO
2
2
Contacto normalmente cerrado
Contact normally closed (dirty fi lter/s at contact opening)
Register 29 (BIT4) = 1
Air quality measure
(ppm)
Register 25
(filtro/s sucio/s a la apertura del contacto)