PROGRAMMABLE FUNCTIONS
All functions have been factory set and tested. The
factory settings listed in this manual are the drive
manufacturer's factory setting.
I_O MENU
SUB-
CODE
NAME/DESCRIPTION
CODE
tCC
Al1-
Al1t
r1
AO1-
AO1
AO1t
drC MENU
SUB-
CODE
NAME/DESCRIPTION
CODE
bFr
nPr
UnS
nCr
FrS
nSP
tFr
Ctt
UFr
SLP
StA
FLG
tUn
PAGE 7 OF 51
FREQUENCY DRIVE CONTINUED
Type of Control:
2C – 2-wire control
3C – 3-wire control
Analog Input 1 Type:
5U – 0-5VDC input voltage
10U – 0-10VDC input voltage
0A – 0-20mA current input
Relay Output 1 Assignment:
nO – Not assigned
FLt – No error detected
rUn – Drive run
Analog Output 1 Assignment:
nO – Not Assigned
OCr – Motor current
OFr – Output Frequency
Analog Output 1 Type:
10U – 0-10VDC
0A – 0-20mA
4A – 4-20mA
Standard Motor Frequency
Rated Motor Power (% of drive rated HP)
Rated Motor Voltage
Rated Motor Current
Rated Motor Frequency
Rated Motor Speed
Maximum Frequency
Motor Control Type:
PErF – Performance, Sensorless Vector
Std – Standard, Volts/Hertz
PUNP – Pump, low torque
IR Compensation:
Optimizes torque at very low speeds
Slip Compensation
Frequency Loop Stability: Adjusts overshoots and oscillations at the end of
acceleration or deceleration. A higher number decreases oscillations
Frequency Loop Gain: Adjusts the slope of the speed increase. A lower number
decreases oscillations.
Motor Auto Tuning: Automatically tunes the drive to the motor profile
Some of the most commonly adjusted programmable
functions and parameters are listed below.
NOTE: Refer to the manufacturer's operation
manual or website for complete lists and
explanations.
FACTORY
SETTING
2C
5U
FLt
nO
0A
ADJUSTMENT
FACTORY
RANGE
SETTING
50/60
50Hz
0.5-1.2
1
100-480V
230V
plate
Varies
10-400Hz
50 Hz
0-24000rpM
Varies
10-400Hz
72 Hz
Std
25-200%
100%
0-150%
100%
0-100%
20%
0-100%
20%
nO/YES/dOnE
nO
1023 IH-8923