Cooling only Indoor unit setting
The Cooling only setting of individual indoor units can be changed.
When setting the specifi c indoor unit to Cooling Only unit without connecting to the fl ow selector unit, setup to the
indoor unit to become the Cooling Only unit is necessary. Perform setup in the following procedure.
Setup to the indoor unit is performed by handling the wired remote controller.
Even if a wired remote controller is not used, attach a wired remote controller for setup.
Change the setup with the wired remote controller before using the air conditioner with a wireless remote controller.
Follow to the basic opreration procedure
(1 → 2 → 3 → 4 → 5 → 6 → 7).
• Specify [000F] for the Code No. in Procedure 4.
• Select the following data for the Set data in Procedure 5.
0000 : Heat pump (Factory default)
Setting Data
0001 : Cooling only
87-EN
12
Test run
Before test run
CAUTION
T
T
Methods of test run
When connecting an Flow
Selector unit perform the
following detailed inspection
mode.
<Detailed inspection mode start operation>
1
Set the rotary switch on the interface board
of the outdoor unit to SW01=[2], SW02=[15],
SW03=[16].
7-segment display
[A]
[B]
[
]
[
]
2
Push SW04 for at least 2 seconds.
7-segment display
[A]
[B]
[FS]
[CH]
the
7-segment display
[A]
[B]
[FS]
[ - - ]
– 44 –
r.
r.
2
r
7-segment display
[A]
[B]
[Err]
[FS]
The indication changes
every 0.5 second.
[
]
Address of the error indoor unit
* A
EN
EN
ID
88-EN