15. Thermal disinfection -automatic-
This fitting offers thermal disinfection to reduce the risk of a legionella infection.
Caution!
The directions in the Thermal Disinfection Planning Aid (01805618) must be
adhered to.
Warning!
Personal protective measures (scald protection) must be implemented for the
duration of the thermal disinfection. This might include cordoning off the shower
facilities.
Failure to observe this instruction can result in injuries due to scalding.
The operator is responsible for the execution, monitoring, and logging (room,
tapping point, date, time, temperature and duration).
The manufacturer does not accept any liability for claims by third parties relating to
the improper execution of thermal disinfection on the part of the operator.
☞
At the factory, the thermal disinfection function is set so that the fitting cools down for
1 minute after a 5 minute application time.
☞
Thermal disinfection can only be triggered using the remote control.
You can adjust the thermal disinfection parameters using the remote control (not part
of the scope of delivery, see
An application time of 3, 5, 10, 15, or 20 minutes can be chosen for the thermal
disinfection process. During the application time, water flows without interruption for
2 minutes; the water then flows in pulses until the end of the application time (water
and energy saving function). The cooling time can be set to 0, 1, 3, 5, or 10 minutes.
Required accessories
Bypass solenoid valve cartridge . . . . 2000109499