Operation
(continued)
Shutdown Messages
Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: During all these
conditions, the "Input," "Output" and "Bypass" LEDs will be illuminated.
SHUTDOWN
LCD DISPLAY
CONDITIONS
Extended
Overload
OVERLOAD XXX%
Output Short
Circuit
O/P SHORT CIRCUIT
Bypass SCR
Short Circuit
BYPASS SCR FAIL
Input SCR
Rectifier Fails
RECTIFIER SCR FAIL
Inverter Output
Short Circuit
Output SCR Failure
OUTPUT SCR FAIL
Input Fuse Open
I/P FUSE BROKEN
Output Fuse Open
O/P FUSE BROKEN
Parallel Wire
Connection Failure
PARALLEL FAULT
Internal
+ DC BUS HIGH
Faults
OVERTEMPERATURE
27
MESSAGES
SHUT DOWN
SHUT DOWN
SHUT DOWN
SHUT DOWN
SHUT DOWN
INVERTER FAIL
SHUT DOWN
SHUT DOWN
SHUT DOWN
SHUT DOWN
SHUT DOWN
SHUT DOWN
+ DC BUS LOW
SHUT DOWN
- DC BUS HIGH
SHUT DOWN
- DC BUS LOW
SHUT DOWN
BUS OVP FAIL
SHUT DOWN