2.5.2. Teach from IO-Link Master
a) To enable Teach from the IO-Link master first disable the trimmer input:
Select: "0=Disabled" in the Selection of local/remote adjustment parameters 68 (0x44).
b) The individual team commands can be written to index 2.
2.5.2.1. Single point mode procedure
Select the Switching channel to be taught
a) Select: 1=SSC1 or 2=SSC2 in the "Teach-in Select" 58(0x3A) or 255 = All SSC.
b) Change the Hysteresis if requested for SSC1 or SSC2.
•
"SSC1 configuration" 61(0x3D) "Hysteresis" 3(0x03).
•
"SSC2 configuration" 62(0x3E) "Hysteresis" 3(0x03).
NB! It is not recommended to change the hysteresis below the values stated in the SSC
parameter list.
1) Single value teach command sequence:
#65 "SP1 Single value teach"
#64 "Teach apply" (optional command)
Command Sequence
1) "SP1 Single value Teach"
2) "Teach Apply"
2) Dynamic teach command sequence
#71 "SP1 dynamic teach start"
#72 "SP1 dynamic teach stop"
#64 "Teach apply" (optional command)
3) Two value teach command sequence
#67 "SP1 two value teach TP1"
#68 "SP1 two value teach TP2"
#64 "Teach apply" (optional command)
Command Sequence
1) "SP1 Two value Teach TP1"
2) "SP1 Two value Teach TP2"
3) "Teach Apply"
18
Rev.00 - 10.2023 | CA12CA/EA/KA Capacitve sensors with IO-Link interface | © 2023 | CARLO GAVAZZI Industri