Contents Description
b17
Summer/Winter symbol
DHW mode activation flow rate
(b01=1)
No effect on adjustment (b01=2) 0-100L/min/10
b18
DHW mode activation flow rate
(b01=3)
No effect on adjustment (b01=4) 0-100L/min/10
DHW mode deactivation flow rate
(b01=1)
No effect on adjustment (b01=2) 0-100L/min/10
b19
DHW mode deactivation flow rate
(b01=3)
No effect on adjustment (b01=4) 0-100L/min/10
b20
Flue material selection
b21
PVC flue maximum temperature
CPVC flue maximum tempera-
b22
ture
Standard flue shutdown maxi-
b23
mum temperature
PVC flue shutdown maximum
b24
temperature
CPVC flue shutdown maximum
b25
temperature
Flow temperature limit in automa-
b26
tic calibration
Maximum temperature during
b27
calibration in DHW mode
b28
Flowmeter sensitivity factor
b29
Restoring Factory Values
P30
Heating ramp
Virtual setpoint min. temperature
(b01=1)
Virtual setpoint min. temperature
(b01=2)
P31
Virtual setpoint min. temperature
(b01=3)
Virtual setpoint min. temperature
(b01=4)
P32
Heating standby time
P33
Heating Post-Circulation
P34
Pump operation
P35
Modulating pump min. speed
P36
Modulating pump start speed
P37
Modulating pump max. speed
Pump deactivation temperature
during Post-Circulation (b01=1)
Pump deactivation temperature
during Post-Circulation (b01=2)
P38
Pump deactivation temperature
during Post-Circulation (b01=3)
Pump deactivation temperature
during Post-Circulation (b01=4)
182
BLUEHELIX TECH RRT 30 H
Range
0 = Disabled, 1 = Enabled
0-100L/min/10
0-100L/min/10
0-100L/min/10
0-100L/min/10
0=Standard, 1=PVC, 2=CPVC
60-110°C
60-110°C
60-110°C
60-110°C
60-110°C
25°C ÷ 55°C
75°C ÷ 95°C
0 ÷ 60 (0 = disabled)
Change the value from 0 to 10 by pressing the "DHW +" button. Con-
firm by pressing the "heating +" button.
1-20°C/minute
0=Deactivated, 1-80°C
0=Deactivated, 1-80°C
0=Deactivated, 1-80°C
0=Deactivated, 1-80°C
0-10 minutes
0-255 minutes
0-3 = Operation strategy
30-100%
90-100%
90-100%
0-100°C
0-100°C
0-100°C
0-100°C
cod. 3541C672 - Rev. 00 - 09/2020
Default
0 = Disabled
25
25
25
25
20
20
20
20
0=Standard
88°C
93°C
100°C
93°C
98°C
30°C
80°C
20
-
4°C/minute
0=Deactivated
0=Deactivated
0=Deactivated
0=Deactivated
4 minutes
15 minutes
2
30%
90%
100%
50°C
55°C
55°C
55°C
EN