Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 3.1). Press the heating buttons detail 3 - fig. 1
to increase or decrease the power (min. = 00 - max. = 100). Press the reset button within 5 seconds and the max. power
will remain that just set. Exit TEST mode (see sec. 3.1).

Service menu

ONLY QUALIFIED PERSONNEL CAN ACCESS THE SERVICE MENU AND MODIFY PARAMETERS.
The card Service Menu is accessed by pressing the Reset button for 10 seconds.
The display will show: "100" and the message "co" flashing.
Then set "103" with the DHW buttons, with the heating buttons set "123" and confirm by pressing the Reset button.
Five submenus are available: press the Heating buttons to select, in increasing or decreasing order, "tS", "sC", "In",
"Hi" or "rE".
To enter the selected menu, press the reset button once.
"tS" - Transparent Parameters Menu
Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to
view or modify the value of a parameter: the change will be automatically saved.
Contents Description
b01
Boiler type selection
b02
Exchanger type
Absolute Maximum Heating
Power (b02=1)
Absolute Maximum Heating
Power (b02=2)
b03
Absolute Maximum Heating
Power (b02=3)
Absolute Maximum Heating
Power (b02=4)
System water pressure protec-
b04
tion selection
b05
Summer / Winter function
Variable input contact operation
selection (b01=1)
Variable input contact operation
selection (b01=2)
b06
Variable input contact operation
selection (b01=3)
Variable input contact operation
selection (b01=4)
180
BLUEHELIX TECH RRT 30 H
Range
1 = BITHERMAL INSTANTANEOUS
2 = MONOTHERMAL HEATING only (also with OPTIONAL STO-
RAGE TANK)
3 = MONOTHERMAL COMBI
4 = MONOTHERMAL with STORAGE TANK
1 ÷ 4
0 ÷ 100% (Do not modify the value)
0 ÷ 100% (Do not modify the value)
0 ÷ 100% (Do not modify the value)
0 ÷ 100% (Do not modify the value)
0=Pressure switch, 1=Pressure transducer
0 = WINTER - SUMMER - OFF
1 = WINTER - OFF
0=Flowmeter off, 1=System thermostat, 2=Second room thermostat,
3=Warning/Notification, 4=Safety thermostat
0=Continuous Comfort, 1=System thermostat, 2=Second room ther-
mostat, 3=Warning/Notification, 4=Safety thermostat
0=Flowmeter off, 1=System thermostat, 2=Second room thermostat,
3=Warning/Notification, 4=Safety thermostat
0=Continuous Comfort, 1=System thermostat, 2=Second room ther-
mostat, 3=Warning/Notification, 4=Safety thermostat
cod. 3541C672 - Rev. 00 - 09/2020
Default
2=RRH
3
83%
85%
85%
90%
0=Pressure switch
0 = Enabled
2=Second room therm.
2=Second room therm.
2=Second room therm.
2=Second room therm.