Descargar Imprimir esta página

cecotec AIRCLIMA 9000 SMARTFRESH Manual De Instrucciones página 96

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 44
ENGLISH
-
The shape and position of the buttons and indicators may vary from model to model, but
their function is the same.
-
The air conditioner will beep every time it receives a command from the controller.
2. BEFORE USE
-
This appliance is packaged in a way as to protect it during transport. Take the appliance
out of its box and remove all packaging materials. You can keep the original box and other
packaging elements in a safe place. This will help you prevent product damage when
transporting it in the future. In case the original packaging is disposed of, make sure all
packaging materials are recycled accordingly.
-
Make sure all parts and components are included and in good conditions. If there is any
piece missing or in bad conditions, contact the official Cecotec Technical Support Service
immediately.
3. PRODUCT INSTALLATION
Important considerations
1. The air conditioner must be installed by a professional and the installation section of
the product is for the use of the installation professional only! Installation specifications
must be subject to our after-sales service regulations.
2. When filling the fuel coolant, any misoperation can cause serious injury or damage to the
human body or objects.
3. A leakage test must be carried out after completion of the installation.
4. It is imperative to perform the safety inspection before maintaining or repairing an air
conditioner with a combustible refrigerant to minimise the risk of fire.
5. It is necessary to operate the air conditioner under a controlled procedure to minimise
any risk caused by flammable gases or vapours during operation.
6. The requirements for the total weight of refrigerant filled and the area of a room to be
equipped with an air conditioner (shown in Tables GG.1 and GG.2 below).
Maximum load and minimum required area
M
= (4 m
) x LFL, m
= (26 m³)) x LFL, m
3
1
2
Where LFL is the lower flammability limit in kg/m³, R32 LFL is 0.038 kg/m³.
For devices with a load quantity m1<M = m
The maximum capacity in a room shall be in accordance with the following:
m
=2.5x (LFL)
, x h
(5/4)
max
The minimum floor area required by Amin to install an appliance with refrigerant load M (kg)
shall be in accordance with the following: A
96
AIRCLIMA 9000 SMARTFRESH/ AIRCLIMA 12000 SMARTFRESH/ AIRCLIMA 18000 SMARTFRES/
AIRCLIMA 24000 SMARTFRESH/ AIRCLIMA 12000 SMARTFRESH CONNECTED
= (130 m³)x LFL
3
:
2
x A)
1/2
0
min
= (M/ (2.5 x LFL)
x h
(5/4)
0
))
Where:
2

Publicidad

loading