Descargar Imprimir esta página

Bosch Climate 5000 L Serie Manual De Instalación página 52

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 64
Installation
Appliance type
Maximum pipe
CL5000L 35 E
CL5000L 53 E
CL5000L 70 E
CL5000L 88 E
CL5000L 105 E
CL5000L 105 E-3
CL5000L 125 E
CL5000L 140 E-3
CL5000L 160 E-3
Table 70 Piping lengths
▶ Observe pipe diameter and further specifications.
Unit type
Liquid side [mm]
CL5000L 35 E
6.35 (1/4")
CL5000L 53 E
6.35 (1/4")
CL5000L 70 E
9.53 (3/8")
CL5000L 88 E
9.53 (3/8")
CL5000L 105 E
9.53 (3/8")
CL5000L 105 E-3
9.53 (3/8")
CL5000L 125 E
9.53 (3/8")
CL5000L 140 E-3
9.53 (3/8")
CL5000L 160 E-3
9.53 (3/8")
Table 71 Pipe diameter depending on appliance type
Pipe diameter [mm]
6.35 (1/4")
9.53 (3/8")
12.7 (1/2")
15.9 (5/8")
Table 72 Alternative pipe diameter
Specification of the pipes
Min. piping length
Additional refrigerant to be added if the pipe
length exceeds 5 m (liquid side)
Pipe thickness with pipe diameter from
Ø 6.35 mm to 12.7 mm
Pipe thickness with 15.9 mm pipe diameter ≥ 1.0 mm
Thickness of insulation against heat
Material of insulation against heat
Table 73
2.8
Information on refrigerant
This device contains fluorinated greenhouse gases as refrigerant. The
device is hermetically sealed. You will find the information on the
refrigerant according to the Regulation (EU) No 517/2014 on
fluorinated greenhouse gases in the operating instructions of the device.
Information for the installer: If you refill refrigerant, enter the additional
charge size and the total charge size of the refrigerant in the table
"information on refrigerant" of the operating instructions.
52
Maximum height
length
difference [m]
[m]
≤ 25
≤ 10
≤ 30
≤ 20
≤ 50
≤ 25
≤ 75
≤ 30
Pipe size
Gas side [mm]
9.53 (3/8")
9.53 (3/8")
15.9 (5/8")
15.9 (5/8")
15.9 (5/8")
15.9 (5/8")
15.9 (5/8")
15.9 (5/8")
15.9 (5/8")
Alternative pipe diameter [mm]
6
10
12
16
3 m
With Ø 6.35 mm (1/4"):
12 g/m
With Ø 9.53 mm (3/8"):
24 g/m
≥ 0.8 mm
≥ 6 mm
Polyethylene foam
3
Installation
3.1
Before installation
CAUTION
Risk of injury from sharp edges!
▶ Wear protective gloves during installation.
CAUTION
Danger of burns!
During operation the pipes become hot.
▶ Make sure, that the pipes cooled down before touching them.
▶ Check the scope of delivery for damage.
▶ Check whether a hissing sound due to negative pressure can be
detected when opening the pipes of the indoor unit.
3.2
Requirements for installation site
▶ Observe minimum clearances ( Chapter 2.7 on page 51).
▶ Observe minimum room area.
Appliance type
Installation height
CL5000iU D 35 E
CL5000iU D 53 E
CL5000iU D 70 E
CL5000iL D 88 E
CL5000iL D 105 E
CL5000iL D 125 E
CL5000iL D 140 E
CL5000iL D 160 E
Table 74 Minimum room area
Notices regarding the indoor unit
▶ Do not install the indoor unit in a room in which open ignition sources
(for example: open flames, an operating wall mounted gas boiler or
an operating electric heating system) are in operation.
▶ The installation location must not be higher than 2000 m above sea
level.
▶ Keep the air inlet and air outlet clear of any obstacles to allow the air
to circulate freely. Otherwise poor performance and higher noise
levels may occur.
▶ Keep TV, radio and similar appliances at least 1 m away from the
indoor unit.
▶ Do not install the indoor unit in rooms with a high humidity (e.g.
bathrooms or utility rooms).
▶ Indoor units with a cooling capacity of 2.0 to 5.3 kW are designed for
a single room.
▶ The ceiling construction and suspension system (on site) must be
able to support the weight of the appliance.
Notices regarding the outdoor unit
▶ The outdoor unit must not be exposed to machine oil vapour, hot
spring vapour, sulphur gas, etc.
▶ Do not install the outdoor unit directly next to water or where it is
exposed to sea air.
▶ The outdoor unit must always be kept free of snow.
▶ There must be no disruption caused by extract air or operating noise.
▶ Air should be able to circulate freely around the outdoor unit, but the
appliance must not be exposed to strong wind.
Climate 5000 L • Climate 5000i U/L – 6721841493 (2023/05)
Minimum room area
2
[m]
[m
]
≥ 2.3
≥ 4
≥ 2.3
≥ 4
≥ 2.3
≥ 6
≥ 2.3
≥ 7
≥ 2.3
≥ 10
≥ 2.3
≥ 12
≥ 2.3
≥ 12
≥ 2.3
≥ 13

Publicidad

loading

Este manual también es adecuado para:

Climate 5000i u serieClimate 5000i l serieCl5000l 35 eCl5000iu d 35 eCl5000l 53 eCl5000iu d 53 e ... Mostrar todo