Descargar Imprimir esta página

LG DLE2301W Guía Del Usuario E Instrucciones De Instalacion página 18

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTALLATION INSTRUCTIONS
CONNECTING ELECTRIC DRYERS
_WARN|_I_G
-= To help prevent fire, electric shock, serious injury or death, the wiring and
grounding must conform to the latest edition of the National Electrical Code, ANSI/NFPA 70 and all
applicable local regulations. Please contact a qualified electrician to check your home's wiring and
fuses to ensure that your home has adequate electrical power to operate the dryer.
Electrical
Requirements
for
Electric
MOdelS
Only
AWARNING:
To reduce the risk of fire, electric shock, or injury to persons when using this
appliance, follow basic precautions, including the following:
This dryer must be connected
to a grounded
metal, permanent
wiring system, or an
equipment=
rounding
conductor
must be run
with the circuit conductors
and connected
to the equipment=grounding
terminal
or lead
on the dryer. Failure to do so can result in fire,
explosion, or death.
The dryer has its own terminal
block that
must be connected
to a separate
240 VAC,
60=Hertz, single=phase
circuit, fused at 30
amperes
(the circuit must be fused on both
sides of the line). ELECTRICAL
SERVICE
FOR THE DRYER SHOULD BE OF THE
MAXIMUM
RATE VOLTAGE LISTED ON THE
NAMEPLATE.
DO NOT CONNECT DRYER TO
110=, 115=, OR 120=VOLT CIRCUIT. Heating
elements
are available
for field installation
in dryers which are to be connected to an
electrical service of a different voltage than
that listed on the rating plate. Failure to follow
these instructions can result in fire, explosion,
or death.
• if branch circuit to dryer is 15 ft. (4.5 m)
or less in length, use UL (Underwriters
Laboratories) listed No.=10 AWG wire
(copper wire only), or as required
by local
codes. If over 15 ft. (4.50 m}, use UL=listed
No.=8 AWG wire (copper wire only), or as
required by local codes. Allow sufficient
slack in wiring so dryer can be moved from
its normal location
when necessary.
Failure
to do so can result in fire, explosion, or death.
• The power cord (pigtail} connection
between
wall receptacle
and dryer terminal
block
IS NOT supplied
with dryer. Type of pigtail
and gauge of wire must conform
to local
codes and with instructions on the following
pages. Failure to follow these instructions
can
result in fire, explosion, or death.
• A 4-wire connection
is required for all mobile
and manufactured
home installations, as
well as all new construction
after January
1, 1996. A 4=wire connection
must be used
where local codes do not permit grounding
through
the neutral wire. Failure to do so can
result in fire, explosion, or death.
Special Electrical
Requirements
for Mobile or Manufactured
Homes
_ILW_ILR_!!_
| NG
-" To reduce the risk of fire, electric shock, or injury to persons when using this
appliance, follow basic precautions, including the following:
Any installation in a manufactured or mobile
home must comply with the Manufactured
Home Construction
and Safety Standards
Title 24 CFR, Part 32-80 or Standard CAN/
CSAOZ240 MH and local codes and ordinances.
• A 4-wire connection
is required for all mobile
and manufactured
home installations, as well
as all new construction
after January 1, 1996.
Failure to do so can result in fire, explosion, or
death.
18

Publicidad

loading

Este manual también es adecuado para:

Dle2301rDle2301sDlg2302wDlg2302rDlg2302s