Descargar Imprimir esta página

Siemens 6ES7136-6BA00-0CA0 Informacion De Producto página 19

Módulos failsafe

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 43
Backplane bus interface
Analog-to-digital converter (ADC)
Sensor supply/reverse polarity protection
Temperature measurement for BU type A1 only (the
function cannot be used for this module.)
Color-coded label with color code CC00 (optional)
Filter circuit supply voltage (available in light-colored
BaseUnit only)
U
+
Voltage input positive, channel n
n
U
-
Voltage input negative, channel n
n
Figure 2
1oo1 evaluation
WARNING
To achieve SIL2/Cat.3/PLd when using this wiring, you must use a suitably qualified sensor.
WARNING
All cables need to be laid in such a way that they are resistant to interference voltage. Use shielded cables.
WARNING
For voltage inputs, changes in resistance along the transmission path (from sensor to module) can result in the measured
value being falsified.
For correct measured value acquisition during the entire service life, you must take these changes in resistance into account
when designing the safety functions and take appropriate measures.
WARNING
In the case of 1oo1 evaluation, faults with the sensor or wiring of the F-AI module are not detected.
Assignable parameters for Application 5
Table 1
Parameters for Application 5 of the F-AI 4xU 0..10V HF
Parameter
Behavior after channel faults
Interference frequency suppression
Evaluation of the sensors
Measuring range
Diagnostics: Wire break
Smoothing
Product Information for the Documentation of ET 200SP Fail-safe Modules
A5E32586870-AK, 02/2024
U
V
M
L+
P1, P2,
AUX
DIAG
AI0, AI1,
AI2, AI3
F0, F1,
F2, F3
PWR
Value range in safety mode
Passivation of the entire F-module
Passivation of the channel
50 Hz
60 Hz
1oo1 evaluation (max. SIL2/Cat.3/PLd)
0 to 10 V
Disable
Enable
1 / 2 / 4 / 8 / 16 / 32 / 64 conversion cycles
Sensor supply
Chassis ground
24 V DC (infeed only with light-colored
BaseUnit)
Internal self-establishing voltage buses
Connection to left (dark-colored BaseUnit)
Connection to left interrupted (light-colored
BaseUnit)
Diagnostics LED (green, red)
Channel status LED (green)
LED channel fault (red)
Power LED (green)
19

Publicidad

loading